Sanyo KHH2672R / CH2672R User Manual
Page 41

1
2
3
4
5
6
I-37
SM831148
1. Specifications
1-2 Major Component Specifications
(A) Indoor Unit
MODEL No.
KH2672R
Source
230 - 208 V / 1 phase / 60 Hz
Remote controller (Option)
Wired or Wireless (See Unit Specification)
Controller P. C. B Ass'y
CB - KR24GXH56A
Control circuit fuse
250 V, 5 A
Fan
Cross-flow
Number ... Dia. and length
in.
(mm)
1 ... O.D. 4-1/3 (110), L39 (990)
Fan motor
Model
KFT4Q - 31A6P - C
Source
230 - 208 V / 1 phase / 60 Hz
No. of pole ... r.p.m. (230 V, High)
rpm
4 ... 1,224
Nominal output
W
28.8
Coil resistance
Ω
BRW - WHT
:
260.7
,
ORG - YEL
:
23.76
(Ambient temperature 68
°F)
WHT - VLT
:
42.62
,
YEL
- PNK
:
115.9
VLT
- ORG
:
30.36
,
Safety device
Operating temperature
Open
°F
±
14.4
Close
°F
174.2
± 26
Run capacitor
VAC,
µF
440 V , 1.8
µF
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows ... Fins per inch
2 ... 24.1
Face area
ft.
2
(m
2
)
2.57 (0.24)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
266