Motor Data Identification

Parameter Description

Action

Setting/

Default

P1910

Motor Data Identification

Performs stator resistance
measuring.

0 = Disabled.

1 = Identification of Rs with
parameter change.

2 = Identification of Rs without
parameter change.

3 = Identification of the saturation
characteristic with parameter
change.

20 = Set voltage vector.

1. Press to enter the SED2

parameter mode and to display
r0000

.

2. Press to advance to

parameter P1910.

3. Press to access the

parameter values level.

4. Press to advance to setting

P1910=1. Press

to confirm

and save the setting.

When P1910=1, Alarm A0541
(motor data identification active)
is output and internally P0340 is
set to 3.

Initiate the measuring operation
with a continuous (steady-state)
ON command.

The motor aligns itself and
current flows through it.
Diagnostics are possible using
r0069 (CO: phase current).

On completion of the motor
data identification routine,
P1910 resets (P1910=0, motor
data identification routine
inhibited) and Alarm A0541 is
cleared (deleted).

5. To set the SED2 into a defined

state, issue an OFF1 command.

Minimum = 0

Maximum = 20