Startup Procedures

Siemens Building Technologies, Inc.

27

Parameter Description

Action

Setting/

Default

P0700[1]**

Selection of Command Source
(Start Command)

Selects the command source as
follows:

0 = Factory default setting

1 = BOP (keypad)

2 = Terminal digital input

4 = USS on BOP link (AOP)

5 = USS on COM link

6 = CB (Communications board
or module) on COM link (P1/N2)

1. Press to advance to index

[1], IN001, HAND.

2. Press to confirm index

selection.

3. Press to advance to 1.

4. Press to confirm and save

the setting.

5. Press again to return to the

parameter selection level.

Setting = 1

Default = 1

NOTE:

Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1
to 2 resets all digital inputs to default settings.

P1000[0]**

Selection of Frequency
Setpoint

(Speed Command Source)

Selects the frequency setpoint
source as follows:

1 = Motor potentiometer
setpoint/BOP (keypad)

2 = Analog input

3 = Fixed frequency setpoint

4 = USS on BOP Link/AOP

5 = USS on COM link

6 = CB (Communications board
or module) on COM link (P1/N2)

1. Press to advance to

parameter P1000.

2. Press to access the

parameter indexes.

3. Press to advance to index

[0], IN000, AUTO.

4 Press to confirm index

selection.

5. Press to advance to 2.

6. Press to confirm and save

the setting.

Setting = 2

Default = 2

** Parameters have two index settings: IN000 = Auto and IN001 = Hand.