Startup Procedures
Siemens Building Technologies, Inc.
27
Parameter Description
Action
Setting/
Default
P0700[1]**
Selection of Command Source
(Start Command)
Selects the command source as
follows:
0 = Factory default setting
1 = BOP (keypad)
2 = Terminal digital input
4 = USS on BOP link (AOP)
5 = USS on COM link
6 = CB (Communications board
or module) on COM link (P1/N2)
1. Press to advance to index
[1], IN001, HAND.
2. Press to confirm index
selection.
3. Press to advance to 1.
4. Press to confirm and save
the setting.
5. Press again to return to the
parameter selection level.
Setting = 1
Default = 1
NOTE:
Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1
to 2 resets all digital inputs to default settings.
P1000[0]**
Selection of Frequency
Setpoint
(Speed Command Source)
Selects the frequency setpoint
source as follows:
1 = Motor potentiometer
setpoint/BOP (keypad)
2 = Analog input
3 = Fixed frequency setpoint
4 = USS on BOP Link/AOP
5 = USS on COM link
6 = CB (Communications board
or module) on COM link (P1/N2)
1. Press to advance to
parameter P1000.
2. Press to access the
parameter indexes.
3. Press to advance to index
[0], IN000, AUTO.
4 Press to confirm index
selection.
5. Press to advance to 2.
6. Press to confirm and save
the setting.
Setting = 2
Default = 2
** Parameters have two index settings: IN000 = Auto and IN001 = Hand.