SED2 VFD Electronic Bypass Option Operating Instructions
22
Siemens Building Technologies, Inc.
Parameter Description
Action
Setting/
Default
P0003
User Access Level
Allows you to access more
parameters.
1 = Standard
2 = Extended
3 = Expert
1. Press to access parameter
r0000 and to enter the SED2
parameter mode.
2. Press to advance to
parameter P0003.
3. Press to access the
parameter values level.
4. Press to advance to 3
(expert level).
5. Press to confirm and save
the P0003 = 3 setting.
Setting = 3
Default = 1
NOTE:
Before starting quick commissioning, set P0003 = 3 to ensure all necessary parameters are available
during quick commissioning.
P0010
Quick Commissioning
0 = Ready to Run
1 = Quick Commissioning
30 = Factory Setting
1. Press to access parameter
r0000 and to enter the SED2
parameter mode.
2. Repeatedly
press to
advance to parameter P0010.
3. Press to access the
parameter values level.
4. Press to advance to 1.
5. Press to confirm and save
the P0010 = 1 setting.
Setting = 1
Default = 0
NOTES:
1. P0010 must always be set back to 0 before operating the motor.
2. If P3900 is greater than 0 on completion of commissioning, P0010 is automatically set back to 0.