Startup Procedures

Siemens Building Technologies, Inc.

33

Automatic Restart

CAUTION:

Settings 2 through 7 can cause the motor to restart unexpectedly.

Parameter Description

Action

Setting/

Default

P1210

Automatic Restart

Enables SED2 restart after a
supply power break or after a
fault.

P1210 = 0, Disabled:

Automatic restart is disabled.

P1210 = 1, Trip reset after power on

(P1211 disabled:
The inverter will acknowledge
(reset) faults; that is, it will reset a
fault when it is re-applied. This
means the inverter must be fully
powered down, a brownout is not
sufficient. The inverter will not run
until the ON command has been
toggled.

P1210 = 2, Restart after supply

power blackout (P1211 disabled):
The inverter will acknowledge the
fault F0003 at power on after
blackout and will restart the drive.
It is necessary that the ON
command is wired via digital input
(DIN).

P1210 = 3, Restart after brownout or

fault (P1211 enabled):
For these settings it is
fundamental that the drive only
restarts if it has been in a RUN
state at the time of the faults
(F0003, etc.). The inverter will
acknowledge the fault and will
restart the drive after a blackout
or brownwout. It is necessary that
the ON command is wired via
digital input (DIN).

1. Press to enter the SED2

parameter mode and to display
r0000

.

2. Press to advance to

parameter P1210.

3. Press to access the

parameter values level.

4. Press to advance to

desired setting.

5. Press to confirm and save

the setting.

Minimum = 0
Default = 1
Maximum:

5=Control Board

Version 1.20
or earlier

6=Control Board

Version 1.30

7=Control Board

Version 1.40

Suggested:

3=Control Board

Version 1.20
or earlier

6=Control Board

Version 1.30

7=Control Board

Version 1.40