Installation Instructions

Siemens Building Technologies, Inc.

15

Table 1. Wire Sizes and Tightening Torques for E-Bypass with 208V Drive.

Circuit Breaker

Disconnect

Switch

Overload Ground

Lug

Part

Number

Bypass

Frame

Size

HP kW Amps

Wire

Size *

Torque,

lb-in

(Nm)

Wire

Size *

Torque,

lb-in

(Nm)

Wire

Size *

Torque,

lb-in

(Nm)

Range,

Amps

Max

Backup

Fuse,

Amps

Wire

Size *

Torque,

lb-in

(Nm)

VBE10.5---- A 0.5

0.37

2.3

14-10

Cu

32 (3.6)

18-10

13 -

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

1.8 - 2.5

10

14-2

35 (4)

VBE10.7---- A 0.7

0.55

3.0

14-10

Cu

32 (3.6)

18-10

13 -

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

2.2 - 3.2

12

14-2

35 (4)

VBE11.0---- A 1.0

0.75

3.9

14-10

Cu

32 (3.6)

18-10

13 - 17

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

2.8 - 4

16

14-2

35 (4)

VBE11.5---- B 1.5

1.1 5.5

14-10

Cu

32 (3.6)

18-10

13 -

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

4.5 - 6.3

25

14-2

35 (4)

VBE12.0---- B 2.0

1.5 7.4

14-10

Cu

32 (3.6)

18-10

13 -

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

5.5 - 8.0

30

14-2

35 (4)

VBE13.0---- B 3.0

2.2

10.4

14-10

Cu

32 (3.6)

18-10

13 - 17

(1.5 - 1.7)

18-14

7 - 10.3

(8 - 1.2)

7 - 10

40

14-2

35 (4)

VBE15.0---- C 5.0

4.0

16.7

14-10

Cu

32 (3.6)

14-8

17 - 22

(1.9 - 2.5)

14-10

18 - 22

(2 - 25)

14 - 20

80

14-2

35 (4)

VBE17.5---- C 7.5

5.5

22.0

14-10

Cu

20 - 60

(2.2 - 6.8)

14-8

17 - 22

(1.9 - 2.5)

14-10

18 - 22

(2 - 25)

20 - 25

100

14-2

35 (4)

VBE110.---- C 10

7.5 28

10-1/0

Cu

20 - 60

(2.2 - 6.8)

14-8

17 - 22

(1.9 - 2.5)

18-3

27 - 40

(3.1 - 4.5)

22 - 32

125

14-2

35 (4)

VBE115.---- D 15

11.0 42

10-1/0

Cu

20 - 60

(2.2 - 6.8)

14-6

22 - 27

(2.5 - 3.1)

18-3

27 - 40

(3.1 - 4.5)

40 - 50

200

14-2

35 (4)

VBE120.---- D 20

15.0 54

10-1/0

Cu

20 - 60

(2.2 - 6.8)

12-1

22 - 27

(2.5 - 3.1)

10-1/0

36 - 53

(4.1 - 6)

45 - 63

250

14-2

35 (4)

VBE125.---- D 25

18.5 68

3-3/0-3

Cu

80 (9)

12-1

22 - 27

(2.5 - 3.1)

10-1/0

36 - 53

(4.1 - 6)

57 - 75

300

14-2

35 (4)

VBE130.---- E 30

22.0 80

3-3/0-3

Cu

80 (9)

12-1

22 - 27

(2.5 - 3.1)

10-1/0

36 - 53

(4.1 - 6)

70 - 90

350

14-2

35 (4)

VBE140.---- F 40

30.0

104

6 - 350

kcmil

Cu

120 - 275

(14 - 31.1)

12-1

22 - 27

(2.5 - 3.1)

6-3/0

124 - 210

(14 - 23.7)

50 - 200

800

14-2/0

50 (5.6)

VBE150.---- F 50

37.0

130

6 - 350

kcmil

Cu

120 - 275

(14 - 31.1)

6 - 350

kcmil

120 - 275

(13.5 - 31.1)

6-3/0

124 - 210

(14 - 23.7) 50 - 200

800

14-2/0

50 (5.6)

VBE160.---- F 60

45.0

154

6 - 350

kcmil

Cu

120 - 275

(14 - 31.1)

6 - 350

kcmil

120 - 275

(13.5 - 31.1)

6-3/0

124 - 210

(14 - 23.7)

50 - 200

800

14-2/0

50 (5.6)

* Wire size is AWG unless noted otherwise. Use Copper (Cu) wire that is rated 167°F (75°C) minimum
600 Vac.