Siemens SED2 VFD Electronic Bypass Option 125-3208 User Manual
Page 33

Startup Procedures
Siemens Building Technologies, Inc.
25
Parameter Description
Action
Setting/
Default
P0310*
Rated Motor Frequency
12 Hz to 650 Hz
Rated motor frequency (Hz) from
motor nameplate.
Pole pair number is recalculated
automatically if the parameter is
changed.
1. Press to advance to
parameter P0310.
2. Press to access the
parameter values level.
3. Press to advance to
nominal frequency (60 Hz).
4. Press to confirm and save
the setting.
Setting =
Motor
nameplate 60
Hz
Default =
50 Hz/60 Hz
Default is
dependent on
the setting of
the motor
frequency and
unit of
measurement
DIP switches.
P0311*
Rated Motor Speed
0 to 40,000 1/min
Rated motor speed (rpm) from
motor nameplate.
A setting of 0 causes an internal
calculation of this value.
Vector control and V/f control
with speed controller require this
value.
Slip compensation in V/f control
requires this value for correct
operation.
Pole pair number is recalculated
automatically if the parameter is
changed.
1. Press to advance to
parameter P0311.
2. Press to access the
parameter values level.
3 Press to advance to
nominal motor speed.
4. Press to confirm and save
the setting.
Setting =
Motor
nameplate
Default =
Varies by
model
* Motor related parameters.