Wdv series gas fireplace flex vent installation, Fp1975 pipe connection, Fp1976 horizontal flex – Monessen Hearth WIDEVIEW WDV500 User Manual

Page 20

background image

20

78D0011

WDV Series Gas Fireplace

Flex Vent InstallatIOn

Termination
Cap

Storm Collar

Roof Support

Flashing

Rigid Pipe
Length

Flex to Pipe
Adapter
(FPA/8)

Firestop

UL1777 Flex
PIpe

DVF8A/8
Adapter

Figure 26 -
Typical Vertical Flex Vent Installation

FP1975
pipe connection

Screws
(3 Places
equidistant
just above
gear clamp)

Rigid Pipe Length

Flex to Pipe Adapter
(FPA/8)

Gear Clamp

1C\v" Flexible Pipe and Adapter
Outer Collar Overlap

UL1777 Flex Vent

Figure 27 -
Typical Pipe Connection

Gear Clamp

FP1976
horizontal flex

Screws
(3 Places equidistant just
above gear clamp)

Gear Clamp

UL1777 Flex Vent

1C\v" Flexible Pipe and
Collar Overlap

MHSC Horizontal
Vent Termination

Figure 28 -
Typical Horizontal Flex Vent Installation

FP1974

2. Install firestop spacers, Figure 26, when penetrating ceiling, attic spaces, or walls.
3. Do not allow the flexible vent to bend in radius tighter than 5" (127 mm). Figure 25
4. Horizontal runs of flexible vent shall be supported at maximum 2 foot intervals; vertical runs,

five feet intervals. Metal strapping, properly secured, is an acceptable means to support the
flexible vent.

5. Flexible vent spacers are to be installed at intervals prescribed by the flexible vent manufac-

turer; and in such a way as to maintain concentric inner and outer vent spacing.

D. Attaching flexible venting to vertical termination assemblies.

1. When using Simpson pipe, an MHSC flex-to-pipe adapter (FPA) and/or rigid pipe section(s) is

required to connect the flexible vent assembly to the vertical termination by using three self-
penetrating screws.

2. Review Figure 27 and corresponding instructions for proper overlap, clamp and screw place-

ment.

3. Three each self-penetrating screws are drilled opposite one another and below the gear

clamp.

4. Use only listed and approved terminations and accessories, installed per the installation instruc-

tions and Figure 26.

E. Installing flexible venting to horizontal termination assemblies.
1. Connect the 5" flexible vent to the horizontal termination as in Figure 28.
2. Connect the 8" flexible vent to the termination ring as in Figure 28.
3. Review Figure 28 for proper overlap and clamp placement.
4. Three each self-penetrating screws are drilled opposite one another and below the gear

lamp.

5. Use only listed an approved terminations and accessories, installed per the termination instruc-

tions and Figure 28.