beautypg.com

Monessen Hearth WIDEVIEW WDV500 User Manual

Page 11

background image

78D0011

11

WDV Series Gas Fireplace

Vent InstallatIOn

InstallatIOn plannInG

There are two basic types of direct-vent installation:

Horizontal Termination

Vertical Termination

It is important to select the proper length of vent pipe for
the type of termination you choose. It is also important to note the wall thickness.

FOr hOrIZOntal terMInatIOn

Select the amount of vertical rise desired. All horizontal run of venting must have 1/4" rise for every
12" of run towards the termination below 7Z\x feet of vertical rise. With 7Z\x feet or more vertical
rise off top of fireplace, the horizontal run may run level. NEVER run vent piping down.
You may use up to three 90° elbows in this vent configuration. Refer to Vertical/Horizontal Ter-
mination Configurations on Page 14.

FOr VertIcal terMInatIOn

Measure the distance from the fireplace floor to the ceiling. Add the ceiling thickness, the vertical
rise in an attic or second story, and allow for sufficient vent height above the roof line.
nOte: You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios
when using 45° elbows. The appliance is approved for use with three 90° elbows maximum or
a combination of 90° and 45° elbows up to a maximum of 270°.
For two-story applications, firestops are required at each floor level. If an offset is needed in the
attic, additional pipe and elbows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house.
Refer to Installing A Vent System in an Outside Chase below. If pipe is enclosed in chase, it is
not exposed.
It is very important that the venting system maintain its balance between the combustion air
intake and the flue gas exhaust. Certain limitations apply to vent configurations and must be
strictly followed.

InstallInG a Vent systeM In an OutsIDe chase

A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a
building. A chase is required for such venting.

W

arn

In

G

never run the vent pipe level or downward.
this may cause excessive temperatures
which could cause a fire.

n

O

t

Ice

When installing in a chase, you should insulate the chase as you would the
outside walls of your home. this is especially important in cold climates.
Insulation should be considered a combustible material. Maintain proper
clearances to all combustible materials.

n

O

t

Ice

treatment of firestops and construction of the chase may vary from
building type to building type. these instructions are not substitutes
for the requirements of local building codes. you must follow all local
building codes.