WDV Series Gas Fireplace

VentInG InstallatIOn

VertIcal (thrOuGh-the-rOOF)
applIcatIOns

This gas fireplace has been approved for,

Vertical installations up to 40' (12 m) in height. Up to

a 10' (3 m) horizontal vent run can be installed within
the vent system using a maximum of two 90° elbows.
Figure 18

nOte: Horizontal and vertical sections of this vent system
require a minimum 1" clearance to combustibles at the top,
sides and bottom.

Example:

Elbow 1 = 90°

Elbow 2 = 45°

Elbow 3 = 45°

Elbow 4 = 90°

Total Angular Variation = 270°

12" Min.

1
2
3
4

1
2
3
4

FP1179

max bends

Figure 19 -
Maximum Elbow Usage

FP1179

FP1966
snorkel

Figure 17 -
Snorkel Installation, Recessed Foundation

Foundation
Recess

Watertight Seal
Around Pipe

Sheet Metal
Screws

Wall Screws

Snorkel

W

arn

In

G

Do not back fill around snorkel.

a clearance of at least 4" must be

maintained between the snorkel and
the soil.

Up to two 45° elbows may be used within the horizontal

run. For each 45° elbow used on the horizontal plane,
the maximum horizontal length must be reduced by 18"
(450 mm).

Example: Maximum horizontal length

No elbows = 10’ (3 m)

1x45° elbows = 8.5’ (2.6 m)

2x45° elbows = 7’ (2.1 m)

A minimum of an 12' (3.6 m) vertical rise is

required.

Two sets of 45° elbows offsets may be used within

the vertical sections. From 0 to a maximum of 8'
(2.5 m) of vent pipe can be used between elbows.
Figure 19

The maximum angular variation allowed in the

system is 270°. Figure 19

FP1183
max height

40' Maximum Height
12' Minimum Height

10'

Maximum

Support Straps
Every 3'

12" Min.

FP1183

Figure 18 -
Support Straps for Horizontal Runs