beautypg.com

Appendices, Selection of protection devices, Cont') – MGE UPS Systems Comet TM 5 - 30 kVA User Manual

Page 54

background image

Comet installation and user manual: E-6761200XT/FB

11.6

Merlin Gerin by MGE UPS SYSTEMS

selection of protection devices

Selection of protection devices installed upstream (CB1) or downstream (CB2)
from Comet depends on:

the rated line current;

the required breaking capacity.

Schematic diagram for protection devices

appendices

(cont')

Comet

Comet rated

Merlin Gerin

Merlin Gerin

output (kVA)

circuit breaker CB1

circuit breaker CB2

series 11

5

C60N 32A (curve D)

C60L

6A (curve Z)

7.5

C60N 40A (curve D)

C60N

10A (curve B)

10

C60N 63A (curve D)

C60N

10A (curve B)

series 31

5

C60N 25A (curve D)

C60L

6A (curve Z)

7.5

C60N 40A (curve D)

C60N

10A (curve B)

10

C60N 50A (curve D)

C60N

10A (curve B)

15

NC100H 80A (curve D)

C60N

25A (curve B)

20

NC100H 100A (curve D)

C60N

25A (curve B)

series 33

10

C60N 40A (curve D)

C60L

6A (curve Z)

or C60N

6A (curve B)

15

C60N 40A (curve D)

C60L

6A (curve Z)

or C60N

5A (curve B)

20

C60N 63A (curve D)

C60L

16A (curve Z)

or C60N

10A (curve B)

30

NC100H 80A (curve D)

C60L

16A (curve Z)

or C60N

10A (curve B)

To ensure discrimination during overloads or short-circuits, the following
protection devices are recommended:

LV switchboard

CB1

Comet

CB2

CB2

Note:
The breaking capacity of the protection devices must be greater than the
prospective short-circuit current.
Consult the Merlin Gerin Low Voltage Application Guide for further details.

Selection of the trip units for the circuit breakers installed upstream of the
transformers must take the inrush currents (10 to 14In) into account.