Mains 2 out of tolerance – MGE UPS Systems Comet TM 5 - 30 kVA User Manual

Page 29

background image

Comet installation and user manual: E-6761200XT/FA

6.5

Merlin Gerin by MGE UPS SYSTEMS

Mains 2 out of tolerance

Mains 2 (or the standby Mains) supplies the "static bypass" 3 (SS) and the
manual maintenance bypass.

as standard it is connected to the same terminal block as power Mains 1;

as option Mains 2 can be connected to a separate terminal block:

the voltage tolerance of Mains 2 is defined with respect to the UPS rated output

voltage and is +7%, -10% for rated voltages of 240V and 415V and +/- 10% for
other voltages,

the frequency tolerance of Mains 2 can be set between 1 and 4%.

A Mains 2 in tolerance allows UPS/Mains 2 transfers of the load without voltage
breaks.
When Mains 2 is out of tolerance, transfers take place with a load voltage break
of 0.5 second.