options

(cont')

Prior to any operations, check that the protection devices are in the following
positions:

upstream circuit breaker off;

input power switch 1 off;

battery circuit breaker 4 off;

"manual bypass" switch set to the "NORMAL" position.

position the battery cabinet on the right side of Comet;

connect the terminal block in the battery cabinet to the XR3 terminal block in

Comet as follows:

yellow/green cable (earth) to the yellow/green terminal on XR3,

red cable (+ pole) to the L+ terminal on XR3,

blue cable (– pole) to the L– terminal on XR3;

position the two enclosures with the front panels aligned;

turn on the circuit breaker in the battery cabinet.

connection of an additional battery cabinet

Connection of an additional battery cabinet

tie the shielding of the
cable to the stud
provided on the
connection cover panel
(see appendices).

battery cabinet terminal block

to a second
battery cabinet
(if applicable)

XR3
battery

XR2
load

XR1
Mains

XR3
battery

Comet connection terminal blocks

XR1
Mains 2
(optional)

L

+

L

XR3
emergency
off

L L

+

(except for 5 kVA Comet S11 or S31)

L

+

L

connection terminal blocks of Comet S11/S31 5kVA

XR3
battery