Comet installation and user manual: E-6761200XT/FB

11.1

Merlin Gerin by MGE UPS SYSTEMS

appendices

general characteristics

the Comet range is made up of three types of uninterruptible power supplies:

Comet series 11 (single-phase input, single-phase output),

Comet series 31 (three-phase + neutral input, single-phase output),

Comet series 33 (three-phase + neutral input, three-phase + neutral output);

each UPS may be configured in a number of manners via a special interface

14 .

On the following pages, standard configuration parameters are indicated in bold
type.
A modification in the configuration requires on-site servicing by the after-sales
support department;

except where indicated, the data provided are typical values corresponding to:

a rated single-phase voltage of 230V and a rated three-phase voltage of 400V,

a linear rated load with a power factor of 0.8.

range characteristics

standards

design:

CEI 146

product:

EN 50091

safety:

CEI 950

protection:

CEI 529 (IP 215)

electromagnetic compatibility:

CEI 801
EN 55011
EN 55022
EN 50091-2

environment conditions

ambient temperature

(1)

:

< 25

°

C recommended

0 to 30

°

C permanent

35

°

C up to 24 hours

40

°

C up to 8 hours

relative humidity (%):

0 to 95

maximum altitude without derating:

< 1000m

configuration

low battery shutdown warning (minutes):

1, 2, 3, 4, 5, ...20

inverter start-up:

automatic or manual

battery charger:

internal or external

transfer to bypass outside tolerances:

yes / no

frequency converter:

yes / no

colour

standard:

RAL 9002