Comet installation and user manual: E-6761200XT/FA

6.1

Merlin Gerin by MGE UPS SYSTEMS

operation

normal operation

The AC input power supply is present (figure 19):

the green "load protected" light 21 is on;

the power drawn by the load is supplied by AC input power via the rectifier 2

and inverter 7 modules. The charger 6 float charges or recharges the battery

5 . The DC output voltage of the charger is temperature regulated to ensure an

optimal charge voltage.

I

+ –

!

!

O

21

When AC input power fails or exceeds tolerances, the rectifier 2 and the
charger 6 shut down. The battery 5 supplies the power required by the
inverter

7 to supply the load.

The battery 5 discharges.
The green "load protected" light 21 is on.
The user is warned of operation on battery power by the buzzer 17 and by the
orange "battery status" light 20 . This information is also available via
the standard communication connector 15 .

load

AC input

5

7

6

2

I

+ –

!

!

O

21

20

17

bip...bip...

operation on battery power

(figure 20)