beautypg.com

Shutdown, Inverter shutdown, Powering down – MGE UPS Systems Comet TM 5 - 30 kVA User Manual

Page 23

background image

Comet installation and user manual: E-6761200XT/FA

5.1

Merlin Gerin by MGE UPS SYSTEMS

press the "inverter off" button 23 for three seconds:

the green "load protected" light 21 goes off,

the red "load not protected" light

18 goes on,

the buzzer 17 sounds,

the inverter

7 stops if the transfer conditions are correct,

the load is supplied directly by AC input power via the "static bypass" 3 ;

in the event of fault, see the Alarms section.

inverter shutdown

bip...bip...

21

I

+ –

!

!

O

23

18

17

powering down

It is recommended not to power down Comet for long periods because the
battery should remained charged. However, to carry out a power down, proceed
as follows:

shutdown the inverter 7 ;

put the battery circuit breaker 4 in "off" position;

turn off the input power switch

1 ;

all the indicating lights on the control panel go off.

Caution:
The load is still supplied by AC input power via the "static bypass" 3 ;

put the upstream circuit breaker(s) on the low voltage switchboard in "off"

position.

shutdown