Appendices, Comet series 11 general characteristics, Cont') – MGE UPS Systems Comet TM 5 - 30 kVA User Manual
Page 50
Comet installation and user manual: E-6761200XT/FB
11.2
Merlin Gerin by MGE UPS SYSTEMS
Comet series 11 general characteristics
■
apparent power (kVA):
5
7.5
10
■
active power (kW):
4
6
8
■
efficiency (%):
91
91
91
■
heat losses (W):
445
668
890
■
noise level (dBa):
■
■
on RL load:
45
46
46
■
■
on RCD load:
50
53
53
■
battery backup time (minutes):
■
■
at rated load (power factor 0.6):
8
10
10
■
maximum leakage current (mA):
■
■
directly earthed neutral system (TT):
10
23
23
■
■
during a fault with an impedent neutral system: 28
60
60
■
dimensions and weight
■
■
height (mm):
730
910
910
■
■
width (mm):
360
400
400
■
■
depth (mm):
420
550
550
■
■
weight (kg):
90
190
210
■
AC input
■
■
number of phases:
1
■
■
voltage (V):
187 to 257
■
■
frequency (Hz):
47 to 63
■
■
power factor:
> 0.99
■
■
current distortion (%):
< 5
< 3
< 3
■
■
inrush current:
< In
■
AC output
■
■
number of phases:
1
■
■
voltage (V):
220 / 230 / 240
■
■
voltage tolerance (%):
±
1
■
■
frequency (Hz):
50 / 60
■
■
frequency tolerance (free-running) (%):
±
0.1
■
■
frequency tolerance (synchronized) (%):
±
1 /
±
1.5 /
±
2 /
±
3 /
±
4
■
■
synchronization rate (Hz/s):
1 / 2
appendices
(cont')