Installation, General, Final positioning – MGE UPS Systems Comet TM 5 - 30 kVA User Manual

Page 11

background image

Comet installation and user manual: E-6761200XT/FC

2.1

Merlin Gerin by MGE UPS SYSTEMS

installation

(for qualified personnel only)

"Comet" cubicles are equipped with 4 wheels for moving over short distances

and with jacks to immobilize the unit. The jacks must be raised prior to
repositioning a cubicle;

operating temperature range: 0

°

to 30

°

C at rated output.

Important:

the battery is of the sealed type. Battery storage or prolonged shutdown

of Comet should never exceed 3 months at 20

°

C without recharging, for a

battery initially at 100% charge. Battery recharge requires system start-up.
The battery warranty is void if the 6 month recharge interval is not
respected;

battery life is extended when it is installed in a room with an ambient

temperature of 15 to 25

°

C. Above 25

°

C, battery life reduced by 50% for

every additional 10

°

C;

heat loss resulting from Comet operation must be taken into account when

sizing the ventilation system. See the Appendices;

connections are made through the bottom section in the back or the front,

depending on the type of Comet;

warning in compliance with EN 50091-2: this product is sold through limited

sales channels to installers or well-informed users. Installation restrictions or
additional measures may be necessary to prevent electromagnetic disturbances.

general

Fig. 8

"e" see note

100 mm minimum
(for ventilation)

air extraction

extended battery
option

other option

L1

L

P

P1

Comet

L2

L2

final positioning

(figure 8)

"Comet" layout seen from above