log clearances

W

H

The following formula can be used to determine the maximum heater rating per the definition of

unconfined space:

BTU

/

hr

=

(L1 + L2) Ft x (W) Ft x (H) Ft.

x 1000

BTU

/

hr

50

Consider two connecting rooms with an open area between, with the following dimensions:

L

1

= 15

1

/

2

Ft., L

2

= 12 Ft., W = 12 Ft., H = 8 Ft.

BTU

/

hr

=

(15

1

/

2

+ 12) x (12) x (8)

x 1000 = 52800

BTU

/

hr

50

If there were a door between the two rooms the calculation would be based only on the room

with the heater.

BTU

/

hr

=

(15

1

/

2)

x (12) x (8)

x 1000 = 29760

BTU

/

hr

50

GENERAL INSTALLATION INFORMATION

Figure 1 - Example of a Large Room with 1/2 Wall Divider

Counter

Fireplace

If the area in which the heater may be operated is smaller than that defined as an

unconfined space or if the building is of unusually tight construction, provide adequate

combustion and ventilation air by one of the methods described in the National Fuel

Gas Code, ANSI Z223.1/NFPA 54, Section 5.3 or applicable local codes.