86D0024

FP1997
heat resistant material

Heat Resistant

Material

Heater in Fireplace

or Firebox

FP1997

Measure

This

Distance

Figure 5 - Measuring Heat Resistant Material

Heat resistant material (minimum requirements) with no wooden mantel or other combustible projection:

To install the gas logs into a fireplace with no wooden mantel, shelf or other combustible projection above the

fireplace opening, measure the heat resistant material height, per Figure 5, then see TABLE A.
Heat resistant materials such as slate and marble must

be at least 1/2” thick. Sheet metal should not be

installed onto combustible material.
IMPORTANT:
If you cannot meet these minimum clearances you must operate the heater with chimney flue

damper open. Refer to “Installing Vented Applications” found on Page 18.

TABLE A - Heat Resistant Material Requirements with no Mantel or Combustible Projection

CLEARANCES and HEIGHT REQUIREMENTS

Heat Resistant

Material

Requirements for Safe Installation

Measurement

MJ27

12" or more

Hood not required

8" to less than 12"

Extend heat resistant material to 12"

OR install hood.

Refer to Figure 5

Less than 8"

Extend heat resistant material to 8"

AND install hood.

Refer to Figure 5.

OR, extend heat resistant material

to a height of at least 12"