Page 30

background image

3.3

Main Menu Screen

The Main Menu screen allows the operator to access many

displays to monitor the operating performance of Galaxy

4000, obtain alarm information, change operational settings

as well as issue software based commands.

The Main Menu conveniently displays groups of items

according to function. By using one of the first two soft keys

the selection cursor may be moved up and down until the

desired display group is selected. Then by pressing the

fourth soft key, the selected display (or display group) will

be summoned. See Figure 3-5.

3.4

Measurements

Selecting the Measurements option from the main menu

provides the following screen selections: battery, power,

current, voltage, frequency measurements, and ratios.

3.4.1

Battery Measurements Screen

The Battery Measurements screen provides a rapid

assessment of the available battery voltage, current,

battery charge, temperature as well as expected service

life. See Figure 3-6.

The backup time measurement will be calculated if the

following battery parameter identification (BPI) require-

ments are met:

Required Conditions to Initiate BPI:

BPI set to automatic in personalization.

Battery charge level = 100%.

UPS On-line (Inverter Coupled).

Mains 2 within tolerance.

Percent load is >15%.

Battery temperature 0-40°C (32-104°F).

No battery faults.

No rectifier or inverter overload condition.

If the above conditions are met and maintained then the UPS will run a successful BPI. A normal BPI will drain the

batteries to a level of 80% capacity. When the BPI is completed successfully, the backup time will be displayed when

the batteries are 100% charged. If the load does not change by more than ±20%, then a BPI will be run again in one

year. Another BPI will run only if, the load changes by ±20% or the BPI is a year old.

If one of the conditions below occurs during the performance of the BPI, the BPI will be aborted.

Factors Leading to Abort a BPI:

Inverter to mains 2 source transfer.

Load percent drops to <15%.

Battery temperature outside 0-40°C (32-104°F).

Percent load changes more than +/-5% from starting power level.

Galaxy 4000

Display Panel

3 — 4

86-173010-00 A00

Figure 3-5: Main Menu screen.

Figure 3-6: Battery Measurements screen.

Battery measurements

Voltage

257

V

Current

0.0

A

Backup Time

not avail.

Battery Charge

100%

Temperature 21*

c

Service Life

60 Mth

Main Menu

Measurements

Mimic Diagrams

Status

Settings

Commands

vo lt