beautypg.com

Galaxy 4000 – MGE UPS Systems 40-75KVA User Manual

Page 16

background image

Galaxy 4000

1 — 4

86-173010-00 A00

Figure 1-3: Cabinet Placement, Airflow and Recommended Clearances.

Table 1-1: Heat Rejection Data.

NOTE:

To provide for adequate ventilation, a minimum of 36 inches clearance should
be maintained above the top of the Galaxy 4000 cabinet.

1.8

Cabinet Clearances

The Galaxy 4000 UPS cabinet top clearance of 36 inches for fan exhaust is recommended. Additionally, adequate

space must be included in the front and top of each cabinet (approx. 36 inches) to allow the doors/panels of the

cabinet to be opened for service and maintenance procedures.

For an installation where seismic requirements must be met, additional clearance at the side of the cabinet must be

included to accommodate the seismic anchors. Contact your local MGE Sales Representative to order. See Figure 1-4.

1.9

Conduit Plate Locations for Bottom Entry

Cable entry through the bottom is the standard preferred design for the Galaxy 4000 UPS cabinet. The bottom entry

conduit plate provides space for up to five (5) separate conduit entries. The plate is secured with screws which

should be retained for the conduit plate after the power connections are made. See Figure 1-4 for the location of

the bottom entry conduit plates.

Heat Rejection Data @ 208/208VAC

UPS cabinet

40KVA

50KVA

65KVA

75KVA

BTU/Hr

14,900

18,700

24,200

28,000

ALLOW 36" TOP CLEARANCE
FOR FAN EXHAUST AND SERVICE MAINTENANCE

AIR EXHAUST

DISPLAY PANEL

LEVELING
JACKS

CASTERS

UPS CABINET

Galaxy 4000

EXTERNAL BATTERY

CABINET

(Optional)

FRONT VIEW

?

!

!

2

3

4

1

(

(

DISTRIBUTION

CABINET

(Optional)

AIR INTAKE

Introduction