beautypg.com

Installation and user manual – MGE UPS Systems 40-75KVA User Manual

Page 23

background image

Installation and User Manual

2.3.8

External Maintenance Bypass Control Connections (optional)

The external maintenance bypass (MBP) control connections are made with the MBP control cable from the external

MBP to the UPS terminal block TB4-9 to TB4-10. See Figure 2-1.

ELECTRICAL

These wires carry HIGH VOLTAGE 120VAC.

2.3.9

Accessories Outlets

The 120VAC outlets to be used on MGE authorized accessories only. The outlets total current not to exceed 2 amps.

CAUTION

Improper use of outlets may cause failure or damage to UPS.

2.4

Relay Communication Card Contacts

The relay communication card contains six programmable dry contact outputs and two programmable dry inputs

and is standard on the Galaxy 4000. The inputs and outputs are factory programmed according to functions listed

in Table 2-2.

Table 2-2: Relay Contacts (communication card).

The output contacts numbers for a second relay board installed will be 2.1 to 2.6. Contacts are of the NO

(normally open) type. For dry contacts setting see section 3.7

INPUTS

Factory Settings

Options (available on both contacts)

1.A

UPS ON

-Room temperature fault.
-Transfer to bypass disabled.
-Transfer to bypass disabled if bypass AC source out of tolerance.
-Desynchronize UPS from bypass AC source.

1.B

UPS OFF

OUTPUTS

Factory Settings

Options (available on all contacts)

1.1

General alarm

-Overload.
-PFC Fault.
-Inverter fault.
-Charger fault.
-Automatic bypass fault.
-Bypass AC source out of tolerance.
-Battery-temperature fault.
-Emergency power off activated.
-Battery circuit breaker(s) open.
-Phase-sequence fault on normal or bypass.
-AC source.
-Blown fuse(s).
-Transfer to bypass AC source disabled.
-Operation in ECO mode.
-UPS on bypass AC source.

1.2

Battery fault

1.3

Load on UPS

1.4

Load on automatic bypass

1.5

Load on battery power

1.6

Low battery warning

Installation

2 — 5

86-173010-00 A00