Galaxy 4000 – MGE UPS Systems 40-75KVA User Manual
Page 28
3.1.1
LED Indicator Functions
The three LED indicators (see Figure 3-1) provide the following information as shown in Table 3-1:
Table 3-1: Three LED Indicators.
IMPORTANT
When the Red LED is ON, the load is not protected.
Green LED
Orange LED
Red LED
ON
Load on UPS
ON
Minor fault such as:
ON
Major fault such as:
Flashing
Load is on battery power
Loss of AC input power
Internal fault
OFF
Inverter not connected to load
Battery problem
Rectifier fault
Overload
Inverter fault
Load on bypass
Bypass static switch fault
Battery not connected
Galaxy 4000
Display Panel
3 — 2
86-173010-00 A00
3.1.2
Screen Saver
When the Galaxy 4000 system has been in continuous
operation, the operator interface will present a screen saver
display. See Figure 3-2.
The product name, "Galaxy 4000", will be moving around
the screen to provide an indication that the unit is
functional.
3.1.3
Operational Summary Screen
Pressing any of the keys will cause the unit to provide an
operational summary display with the following information.
This display will quickly show the operator the time/date, the
KVA load on all three phases, as well as the battery level.
See Figure 3-3.
Figure 3-2: Screen Saver.
Figure 3-3: Operational Summary screen.
NORM Load Protected
03/30/2004 09:30
0.6 0.6 0.6
Battery
volt
KVA
Galaxy 4000
Galaxy 4000
Galaxy 4000