1.2

Major Components

Rectifier

Converts AC input voltage to DC voltage. The rectifier uses IGBT (Insulated G a t e
Bipolar Transistor) power transistors and a Pulse Width Modulated (PWM)
technique to provide input power factor correction and to minimize any harmonic
reflected onto the input power lines.

Inverter

Converts DC voltage from the rectifier or from the batteries into AC output voltage
to maintain the attached load. This module uses the IGBT technology to provide
digital power quality.

Static Switch

Automatically supplies the attached load from the bypass source when the inverter
is off.

Battery System

Stores energy for utilization by the inverter and attached load in the event that utility
AC power is lost or is of unacceptable quality.

1.3

Single Line Diagram

During normal operation, the utility power (Main input) is supplied to the UPS rectifier. The rectifier converts the AC

power to DC that is supplied to the inverter. The inverter converts the DC voltage to three-phase regulated AC

voltage, which is supplied to the attached load.

During power failure conditions, the inverter is supplied by the stored energy in the battery system, and the load is

powered continuously with no interruption.

The Galaxy 4000 UPS is designed for internal operation of 208VAC input and output. External batteries, and an

output distribution panel may be contained in auxiliary cabinets similar in design to the Galaxy 4000 cabinet.

Batteries or external maintenance bypass circuit breakers may also be contained in third party cabinets or wall

mounted units.

Figure 1-2: Galaxy 4000 UPS System – Single Line Diagram.

Introduction

BYPASS
INPUT
TB3

A
B
C

A
B
C

N
G

INPUT

STATIC

SWITCH

INPUT

FUSES

Q1

Q4S

BATTERY

STATIC SWITCH

BATTERY

CHARGER

KB (OPTIONAL)

CONTROL CONNECTIONS

(SEE UPS INSTALLATION DWG)

TB4

REPO ON MBS

SUPPLIED BY MGE &

CON NECTED BY CUSTOMER

(ADJACENT VERSION)

SUPPLIED & CONNECTED

BY CUSTOMER

(STAND ALONE VERSION)

TO
CRITICAL
LOAD

OUTPUT

TB2

Q3BP (OPTIONAL)

7 8 9 10

A
B

C

N

G

Q5N

PFC

BOOST

RECTIFIER

INVERTER

OUTPUT

STATIC

SWITCH

BYPASS

STATIC

SWITCH

UPS

MAIN
INPUT
TB1

OPTIONAL

BYPASS

INPUT

208YVAC

MAIN

INPUT

208YVAC

KA

DISTRIBUTION

BATTERY

42 POLE

PANELBOARD

OUTPUT

CB

(OPTIONAL)

SUPPLIED BY MGE &
CONNECTED BY CUSTOMER

CB1

CB1

TB4

CB1

CB1