beautypg.com

Marathon monitors inc, Configuration parameter tables – Marathon Computer AACC 2000 User Manual

Page 70

background image

Marathon Monitors Inc.

AACC 2000 Carbon Nov. 1, 1997

70

CONFIGURATION PARAMETER TABLES

Name

Description

Values

Meaning

inSt

inSt

Instrument configuration

ZrFn

Instrument Function

Carb

% Carbon

CtrL

Control type

Pid

PID control

On.OF

On/off control

VP

Boundless motorised valve
control - no feedback
required

VP b

Bounded motorised valve
control - feedback required

tYPE

Instrument USE

ctrL

Mon

Controller
Monitor

Act

Control action

rEv

Reverse acting

dir

Direct acting

CooL

Type of cooling

Lin

Linear

oiL

Oil (50mS minimum on-
time)

H2O

Water (non-linear)

FAn

Fan (0.5S minimum on-
time)

ProP

Proportional only to error

on.OF

On/off cooling

ti.td

Integral & derivative

SEc

Seconds, OFF to 9999

time units

min

Minutes, OFF to 999.9

m-A

Front panel Auto/Man button

EnAb

Enabled

diSA

Disabled

r-h

Front panel Run/Hold button

EnAb

Enabled

diSA

Disabled

PwrF

Power feedback

on

On

OFF

Off

Fwd.t

Feed forward type

none

None

FEEd

Normal feed forward

SP.FF

Setpoint feed forward

PV.FF

PV feed forward

Sbr.t

Sensor break output

Sb.OP

Go to pre-set value

HoLd

Freeze output

FOP

Forced manual output

no

Bumpless Auto/Manual
transfer

trac

Returns to the Manual
value that was set when
last in Manual mode

Step

Steps to forced output
level. Value set in ‘

FOP’ of

op-List’ in Operator

Level

bcd

BCD input function

none

prog

sp

Not used
Select program number
Select setpoint number