Tag Addresses 2408

f

& 2404

f

PROFIBUS Communications Handbook

8-14 2408

f

& 2404

f

PROFIBUS Communications Handbook

Program General Data

The offsets of each parameter within the program general data block is given by the next table:

Address Offset

Parameter

0

HoldbackType

0: None
1: Low
2: High
3: Band

1

HoldbackValue

2

Ramp Units

0: Secs
1: Mins
2: Hours

3

Dwell Units

0: Secs
1: Mins
2: Hours

4

Program Cycles

5

Reserved

6

Reserved

7

Reserved

Program Segment Data

Program segment data is specified using 8 tag addresses, with the contents varying depending on the type of the segment. The
format per segment is detailed in the following table, which gives the offset from the start of a segment data block for each
item.

Address Offset

Segment Types
STEP

DWELL

RAMP
RATE

RAMP
TIME TO
TARGET

CALL

END

0

Segment Type

Segment Type

Segment Type

Segment Type

Segment Type

Segment Type

1

Target
Setpoint

Target
Setpoint

Target
Setpoint

2

Duration

Rate

Duration

3

Program
Number

End Type

4

Logic O/P’s

Logic O/P’s

Logic O/P’s

Logic O/P’s

Call Cycles

Logic O/P’s

5
6
7

Example Address calculations

Program 1, Segment 4, Segment Type = 8328 + 32 + 0 = 8360 (20A8 Hex)
Program 2, Holdback Value = 8464 + 0 + 1 = 8465 (2111 Hex)
Program 4 Segment 16, End Type = 8872 + 128 + 3 = 9003 (232B Hex)

Power Level in End Segment

This has the tag address 64 in 2400

f

controllers.

Summary of Programmer Enumerators

Controller Display

Parameter Description

6@0

Current Segment Type
0: End
1: Ramp (Rate)
2: Ramp (Time to target)
3: Dwell
4: Step
5: Call

.D6

End Segment Type
0: Reset
1: Indefinate Dwell
2: Set Output

Controller Display

Parameter Description

#

Holdback Type
0: None
1: Low
2: High
3: Band

=)D8

Dwell Units
0: Seconds
1: Minutes
2: Hours

5,0D8

Ramp Units
0: Seconds
1: Minutes
2: Hours