beautypg.com

MITSUBISHI ELECTRIC 2408f User Manual

Page 11

background image

Controller Set Up & Network Configuration 2408

f

& 2408

f

PROFIBUS Communications Handbook

4-4 2408

f

and 2404

f

PROFIBUS Communications Handbook

P

ROFIBUS

D

IAGNOSTICS

One of the features of PROFIBUS-DP is that high priority diagnostic information is provided for each slave. The 2400

f

Series uses the ‘Ext_Diag_Data’ area of this message (bytes 7 and 8) to send a word containing 16 bits of information
pertaining to the process and alarm status of the controller: The documentation supplied with your master should provide
further details on how to access diagnostic information.

BIT

DESCRIPTION

0

Alarm 1 State ( 0 = Safe 1 = Alarm )

1

Alarm 2 State ( 0 = Safe 1 = Alarm )

2

Alarm 3 State ( 0 = Safe 1 = Alarm )

3

Alarm 4 State ( 0 = Safe 1 = Alarm )

4

Manual Mode ( 0 = Auto 1 = Manual )

5

Sensor Break ( 0 = Good PV 1 = Sensor Broken )

6

Loop Break ( 0 = Good closed loop 1 = Open Loop )

7

Heater Fail ( 0 = No Fault 1 = Load fault detected )

8

Tune Active ( 0 = Auto Tune disabled 1 = Auto Tune active)

9

Ramp/Program Complete ( 0 = Running/Reset 1 = Complete )

10

PV out of range ( 0 = PV within table range 1 = PV out of table range )

11

DC control module fault (0= Good. 1= BAD)

12

Programmer Segment Synchronise (0 = Waiting, 1 = Running)

13

Remote input sensor break (0 = Good, 1 = Bad)

14

IP1 Fault

15

Reserved

Table 4-2: Summary Output Status Word

A ‘new diagnostics’ event will occur whenever any of the monitored events changes state...

Diagnostics Example

The example below may be returned which gives a summary of the Output Status Word information shown in the table
above.

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

XX

XX

24

XX

XX

03

40

30

Byte 6 signifies 3 bytes of information are included
Bytes 7 & 8 are 4030Hex or 01 00 00 00 00 11 00 00 Binary

From table 4-1:

Bit 4 is set Meaning the controller is in Manual Mode
Bit 5 is set Meaning the controller is in Sensor Break
Bit 14 is set Meaning the controller is in IP1 Fault

Global Commands

This is a further PROFIBUS-DP feature, which is not supported by the 2400f series of temperature controllers.