PROFIBUS Communications Handbook Tag Addresses

2408

f

and 2404

f

PROFIBUS Communications Handbook 8-7

Controller

Instrument

Configuration Tab

Tag

Display

Parameter Description

Address

65)

65)

Control type
0: PID
1: On/Off
2: Manual
3: VP (No feedback)
4: VP b (Feedback)

512

6

6

Control action

0: Reverse

1: Direct

7

//)

//)

Type of cooling
0: Linear
1: Oil
2: Water
3: Fan

5: On/Off

524

6OD6

6OD6

Integral and Derivative time
units
0: Seconds
1: Minutes
2: Hours

529

6@0

6@0

Derivative action on:
0: PV
1: Error

550

,B

,B

Front panel Auto/Manual button
0: Enabled
1: Disabled

530

5B$

5B$

Front panel Run/Hold button
0: Enabled
1: Disabled

564

0=5

0=5

Power feedback enable
0: Off
1: On

565

=D6

=D6

Feed forward type
0: None
1: Power feedforward
2: Setpoint feedforward
3: PV feedforward

532

0D65

0D65

Manual/Auto transfer PD control
0: No
1: Yes

555

5D6

5D6

Sensor break output
0: Sensor break (go to set
value)
1: Hold (output)

553

0

0

Forced manual output
0: No
1: Trac (returns to last value)
2: Step (steps to forced output
level)

556

BCD input function
0: None
1: Select program number
2: Select SP number

522

!$

!$

Gain schedule enable
0: No (disabled)
1: Yes (enabled)

567

Controller

Display

Custom

Linearisation Tab

Tag

Address

Parameter Description

O.

O.

Custom linearisation input 1

601

;)D

;)D

Display value corresponding to
input 1

621

O.

O.

Custom linearisation input 2

602

;)D

;)D

Display value corresponding to
input 2

622

O.

O.

Custom linearisation input 3

603

;)D

;)D

Display value corresponding to
input 3

623

O.

O.

Custom linearisation input 4

604

;)D

;)D

Display value corresponding to
input 4

624

O.

O.

Custom linearisation input 5

605

;)D

;)D

Display value corresponding to
input 5

625

O.

O.

Custom linearisation input 6

606

;)D

;)D

Display value corresponding to
input 6

626

O.

O.

Custom linearisation input 7

607

;)D

;)D

Display value corresponding to
input 7

627

O.

O.

Custom linearisation input 8

608

;)D

;)D

Display value corresponding to
input 8

628

Controller

Display

Process Value

Configuration

Tag

Address

Parameter Description

9.O6

9.O6

Instrument units

0:

o

C

1:

o

F

2:

o

K

3: None

516

D0

D0

Decimal places in displayed
value

0: nnnn

1: nnn.n

2: nn.nn

525

5."D)

5."D)

Setpoint Min. (Low range limit)

11

5."D#

5."D#

Setpoint Max. (High range limit)