Test condition – MITSUBISHI ELECTRIC MUY-GE09NA User Manual

Page 6

background image

6

Test condition

ARI

Mode Test

Indoor air condition (°F)

Outdoor air condition (°F)

Dry bulb

Wet bulb

Dry bulb

Wet bulb

SEER

(Cooling)

"A-2" Cooling Steady State

at rated compressor Speed

80

67

95

(75)

"B-2" Cooling Steady State

at rated compressor Speed

80

67

82

(65)

"B-1" Cooling Steady State

at minimum compressor Speed

80

67

82

(65)

"F-1" Cooling Steady State

at minimum compressor Speed

80

67

67

(53.5)

"E-V" Cooling Steady State

at Intermediate compressor Speed 5

80

67

87

(69)

HSPF

(Heating)

(MUZ)

"H1-2" Heating Steady State

at rated compressor Speed

70

60

47

43

"H3-2" Heating

at rated compressor Speed

70

60

17

15

"H0-1" Heating Steady State

at minimum compressor Speed

70

60

62

56.5

"H1-1" Heating Steady State

at minimum compressor Speed

70

60

47

43

"H2-V" Heating

at Intermediate compressor Speed 5

70

60

35

33

5

: At Intermediate compressor Speed

= ("Cooling rated compressor speed" - "minimum compressor speed") / 3 + "minimum compressor speed".

3, 4

(2) OPERATION

Mode

Condition

Intake air temperature (°F)

Indoor

Outdoor

DB

WB

DB

WB

Cooling

Standard temperature

80

67

95

Maximum temperature

90

73

115

Minimum temperature

67

57

14

Maximum humidity

78 %

Heating

(MUZ)

Standard temperature

70

60

47

43

Maximum temperature

80

67

75

65

Minimum temperature

70

60

-4

-5

3-1. OPERATING RANGE

(1) POWER SUPPLY

Rated voltage

Guaranteed voltage (V)

Outdoor unit

208/230 V

1 phase

60 Hz

Min. 187

208

230

Max. 253