8-2. R.V. COIL CONTROL (MUZ)

Heating . . . . . . . . . . . . . . . . . ON

Cooling . . . . . . . . . . . . . . . . . OFF

Dry . . . . . . . . . . . . . . . . . . . . OFF

NOTE

: The 4-way valve reverses for 5 seconds right before start-up of the compressor.

ON

OFF

ON

OFF

Outdoor fan

motor

Compressor

5 seconds

15 seconds

8-1. OUTDOOR FAN MOTOR CONTROL

The fan motor turns ON/OFF, interlocking with the compressor.

[ON] The fan motor turns ON 5 seconds before the compressor starts up.

[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.

ON

OFF

Compressor

Outdoor fan

motor

R.V.coil

ON

OFF

ON

OFF

5 seconds

5 seconds

8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR

Sensor

Purpose

Actuator

Compressor

LEV

Outdoor fan

motor

R.V.coil

(MUZ)

Indoor fan

motor

Discharge temperature
thermistor

Protection

Indoor coil temperature
thermistor

Cooling: Coil frost prevention

Heating: High pressure protec-
tion

Defrost thermistor (MUZ)

Heating: Defrosting

Fin temperature thermistor

Protection

Ambient temperature
thermistor

Cooling: Low ambient tempera-
ture operation

Outdoor heat exchanger tem-
perature thermistor

Cooling: Low ambient tempera-
ture operation

Cooling: High pressure protec-
tion

8

ACTUATOR CONTROL