beautypg.com

7data, Additional refrigerant charge (r410a: oz.) – MITSUBISHI ELECTRIC MUY-GE09NA User Manual

Page 13

background image

13

ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)

Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.

Model

Outdoor unit

precharged

Refrigerant piping length (one way): ft.

25

30

40

50

60

65

MUZ-GE09NA
MUY-GE09NA

1 lb. 12 oz.

0

1.62

4.86

8.10

11.34

12.96

MUZ-GE12NA
MUY-GE12NA

2 lb. 9 oz.

MUZ-GE15NA
MUY-GE15NA

Calculation: X oz. = 1.62/5 oz. / ft. × (Refrigerant piping length (ft.) - 25)

Model

Outdoor unit

precharged

Refrigerant piping length (one way): ft.

25

30

40

50

60

70

80

90

100

MUZ-GE18NA
MUY-GE18NA

3 lb. 7 oz.

0

1.08

3.24

5.40

7.56

9.72

11.88

14.04

16.20

Calculation: X oz. = 1.08/5 oz. / ft. × (Refrigerant piping length (ft.) - 25)

NOTE

: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.

7-1. PERFORMANCE DATA

1) COOLING CAPACITY

7

DATA

MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA

MUY-GE09NA MUY-GE12VA MUY-GE15VA MUY-GE18VA

Model

Indoor air

Outdoor intake air DB temperature (˚F)

IWB (˚F)

75

85

95

105

115

TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC

MUZ-GE09NA
MUY-GE09NA

71

11.0

7.6

0.59 10.3

7.1

0.64

9.7

6.6

0.69

9.0

6.2

0.73

8.3

5.7

0.76

67

10.4

8.6

0.55

9.7

8.0

0.61

9.0

7.4

0.66

8.4

6.9

0.70

7.7

6.3

0.73

63

9.8

9.4

0.53

9.1

8.7

0.58

8.5

8.1

0.63

7.7

7.3

0.67

7.0

6.7

0.70

MUZ-GE12NA
MUY-GE12NA

71

14.7

8.9

0.85 13.7

8.3

0.94 12.9

7.8

1.01 12.0

7.3

1.06 11.0

6.7

1.10

67

13.9 10.3 0.81 13.0

9.6

0.89 12.0

8.9

0.96 11.2

8.3

1.02 10.3

7.6

1.07

63

13.1 11.4 0.77 12.1 10.6 0.85 11.3

9.9

0.92 10.3

9.0

0.98

9.4

8.2

1.02

MUZ-GE15NA
MUY-GE15NA

71

17.2 11.4 0.96 16.0 10.7 1.05 15.1 10.0 1.13 14.0

9.3

1.19 12.9

8.6

1.24

67

16.2 13.0 0.91 15.1 12.1 1.00 14.0 11.2 1.08 13.0 10.4 1.14 12.0

9.6

1.20

63

15.3 14.2 0.86 14.1 13.2 0.96 13.2 12.3 1.03 12.0 11.2 1.10 10.9 10.2 1.14

MUZ-GE18NA
MUY-GE18NA

71

21.1 12.2 1.46 19.7 11.4 1.60 18.5 10.7 1.72 17.2

9.9

1.81 15.8

9.1

1.89

67

20.0 14.2 1.38 18.6 13.2 1.52 17.2 12.2 1.64 16.0 11.4 1.74 14.7 10.4 1.82

63

18.7 15.8 1.31 17.4 14.7 1.45 16.2 13.6 1.57 14.7 12.4 1.67 13.4 11.3 1.74

NOTE

: 1. IWB: Intake air wet-bulb temperature

TC: Total Capacity (×10

3

Btu/h)

SHC: Sensible Heat Capacity (×10

3

Btu/h)

TPC: Total Power Consumption (kW)

2. SHC is based on 80˚F of indoor Intake air DB temperature.

This manual is related to the following products: