beautypg.com

3. troubleshooting check table – MITSUBISHI ELECTRIC MUY-GE09NA User Manual

Page 27

background image

27

10-3. TROUBLESHOOTING CHECK TABLE

No. Symptom LED indication

Abnormal point/

Condition

Condition Remedy

1

Outdoor

unit does

not oper-

ate.

1-time fl ash every

2.5 seconds

Outdoor power sys-

tem

Overcurrent protection stop is continuously performed 3 times

within 1 minute after the compressor gets started, or failure of re-

start of compressor has repeated 24 times.

Reconnect connector of compressor.

Refer to 10-5. "How to check inverter/

compressor".

Check stop valve.

2

Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor, de-

frost thermistor, outdoor heat exchanger temperature thermistor,

P.C. board temperature thermistor or ambient temperature therm-

istor shorts or opens during compressor running.

Refer to 10-5. "Check of outdoor

thermistors".

3

Outdoor control sys-

tem

Nonvolatile memory data cannot be read properly.

(POWER lamp of the indoor unit lights up or fl ashes 7 times.)

Replace inverter P.C. board.

4

6-time fl ash

2.5 seconds OFF

Serial signal

The communication fails between the indoor and outdoor unit for

3 minutes.

Refer to 10-5. "How to check miswir-

ing and serial signal error.

5

11-time fl ash

2.5 seconds OFF

Stop valve/

Closed valve

Closed valve is detected by compressor current.

Check stop valve.

6

14-time fl ash

2.5 seconds OFF

Outdoor unit

(Other abnormality)

Outdoor unit is defective.

Refer to 10-2.2. "Flow chart of the de-

tailed outdoor unit failure mode recall

function".

7

'Outdoor

unit stops

and re-

starts 3

minutes

later' is

repeated.

2-time fl ash

2.5 seconds OFF

Overcurrent protec-

tion

Large current fl ows into intelligent power module.

When overcurrent protection occurs within 10 seconds after

compressor starts, compressor restarts after 15 seconds.

Reconnect connector of compressor.

Refer to 10-5. "How to check inverter/

compressor".

Check stop valve.

8

3-time fl ash

2.5 seconds OFF

Discharge tempera-

ture overheat protec-

tion

Temperature of discharge temperature thermistor exceeds 241°F

(116°C), compressor stops. Compressor can restart if discharge

temperature thermistor reads 212°F (100°C) or less 3 minutes

later.

Check refrigerant circuit and refrigerant

amount.

Refer to 10-5. "Check of LEV".

9

4-time fl ash

2.5 seconds OFF

Fin temperature /P.C.

board temperature

thermistor overheat

protection

Temperature of fi n temperature thermistor on the heat sink ex-

ceeds 167 ~ 176°F (75 ~ 80°C) or temperature of P.C. board tem-

perature thermistor on the inverter P.C. board exceeds 158 ~ 167

°F (70 ~ 75°C).

Check around outdoor unit.

Check outdoor unit air passage.

Refer to 10-5. "Check of outdoor fan

motor".

10

5-time fl ash

2.5 seconds OFF

High pressure pro-

tection
(MUZ)

Temperature of indoor coil thermistor exceeds 158°F (70°C) in

HEAT mode. Temperature of outdoor heat exchanger temperature

thermistor exceeds 158°F (70°C) in COOL mode.

Check refrigerant circuit and refrigerant

amount.

Check stop valve.

11

8-time fl ash

2.5 seconds OFF

Compressor syn-

chronous abnormal-

ity

The waveform of compressor current is distorted.

Reconnect connector of compressor.

Refer to 10-5. "How to check inverter/

compressor".

12

10-time fl ash

2.5 seconds OFF

Outdoor fan motor

Outdoor fan has stopped 3 times in a row within 30 seconds after

outdoor fan start-up.

Refer to 10-5. "Check of outdoor fan

motor.

Refer to 10-5. "Check of inverter P.C.

board.

13

12-time fl ash

2.5 seconds OFF

Each phase current

of compressor

Each phase current of compressor cannot be detected normally.

Refer to 10-5. "How to check inverter/

compressor".

14

13-time fl ash

2.5 seconds OFF

DC voltage

DC voltage of inverter cannot be detected normally.

Refer to 10-5. "How to check inverter/

compressor".

15 Outdoor

unit oper-

ates.

1-time fl ash

2.5 seconds OFF

Frequency drop by

current protection

Current from power outlet is nearing Max. fuse size.

The unit is normal, but check the follow-

ing.

Check if indoor fi lters are clogged.

Check if refrigerant is short.

Check if indoor/outdoor unit air circula-

tion is short cycled.

16

3-time fl ash

2.5 seconds OFF

Frequency drop by

high pressure protec-

tion

Temperature of indoor coil thermistor exceeds 131°F (55°C) in

HEAT mode, compressor frequency lowers.

Frequency drop by

defrosting in COOL

mode

Indoor coil thermistor reads 46°F (8°C) or less in COOL mode,

compressor frequency lowers.

17

4-time fl ash

2.5 seconds OFF

Frequency drop by

discharge tempera-

ture protection

Temperature of discharge temperature thermistor exceeds 232°F

(111°C), compressor frequency lowers.

Check refrigerant circuit and refrigerant

amount.

Refer to 10-5. "Check of LEV".

Refer to 10-5. "Check of outdoor

thermistors".

18

Outdoor

unit oper-

ates.

7-time fl ash

2.5 seconds OFF

Low discharge tem-

perature protection

Temperature of discharge temperature thermistor has been 122°F

(50°C) or less for 20 minutes.

Refer to 10-5. "Check of LEV".

Check refrigerant circuit and refrigerant

amount.

19

8-time fl ash

2.5 seconds OFF

PAM protection PAM:

Pulse Amplitude

Modulation

The overcurrent fl ows into IGBT (Insulated Gate Bipolar transis-

tor: TR821) or the bus-bar voltage reaches 320 V or more, PAM

stops and restarts.

This is not malfunction. PAM protection

will be activated in the following cases:

1 Instantaneous power voltage drop

(Short time power failure)

2 When the power supply voltage is high.

20

9-time fl ash

2.5 seconds OFF

Inverter check mode The connector of compressor is disconnected, inverter check

mode starts.

Check if the connector of the compres-

sor is correctly connected. Refer to

10-5. "How to check inverter/compres-

sor".

NOTE

: 1. The location of LED is illustrated at the right fi gure. Refer to 10-6.1.

2. LED is lighted during normal operation.

The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. Flashing

(Example) When the fl ashing frequency is “2”.

ON

OFF

2.5-second OFF

2.5-second OFF

0.5-second ON

0.5-second ON

LED

Flashing →

Inverter P.C. board (Parts side)

This manual is related to the following products: