M How to check miswiring and serial signal error

Turn OFF inverter-controlled lighting
equipment.
Turn OFF the power supply and then
turn ON again.
Press EMERGENCY OPERATION
switch.

A

Is serial signal
error indicated 6
minutes later?

B

Yes

Reinstall
either the unit
or the light
away from
each other.
Attach a fi lter
on remote
control receiv-
ing section
of the indoor
unit.

No

Turn OFF the power supply.

Is there rated voltage in the power supply?

Yes

No

Turn ON the power supply.

Check the power supply.

Is there rated voltage between outdoor terminal block S1 and S2?

No

Check the wiring.

Press EMERGENCY OPERATION switch once.

Does the OPERATION INDICATOR lamp light
up? unit>

Yes

No

Is serial signal error indicated 6 minutes later?

Yes

No

Is there any miswiring,
poor contact, or wire
disconnection of the
indoor/outdoor connect-
ing wire?

Yes

Correct them.

No

A

Turn OFF the power supply.
Check once more if the indoor/outdoor
connecting wire is not miswiring.
Short-circuit outdoor terminal block S2
and S3. 1

B

1. Miswiring may damage indoor electronic control P.C.

board during the operation.
Be sure to confi rm the wiring is correct before the opera-
tion starts.

Turn ON the power supply.

Does the LED on the inverter P.C. board or the outdoor electronic control P.C.
board repeat "3.6-second-OFF and 0.8-second-ON quick blinking"? 3

Yes

No

(Lighted

or not

lighted)

Replace the inverter P.C. board or the outdoor

electronic control P.C. board. 2

2. Be careful of the residual voltage of smoothing

capacitor.

Yes

3. Be sure to check this within 3 minutes after turning ON.

After 3 minutes, LED blinks 6 times. Even when the
inverter P.C. board or the outdoor electronic control P.C.
board is normal, LED blinks 6 times after 3 minutes.

Is the bus-bar voltage of the inverter P.C. board or the outdoor electronic control P.C. board normal. (Refer
to "TEST POINT DIAGRAM AND VOLTAGE" in this manual.)

Yes

No

Check of power supply.

(Refer to 10-5. .)

Replace the indoor power

P.C. board and the indoor

terminal P.C. board

Is there amplitude of 10 to 20 VDC between indoor terminal block S2

and S3?

Yes

Check the wiring

If there are any error of the indoor/outdoor connecting wire:

such as the damage of the wire, intermediate connection,

and/or poor contact to the terminal block, replace the indoor/

outdoor connecting wire.

No

Is there 2 VDC or less between CN10A (+)
and JPG (GND)(-) on the indoor electronic
control P.C. board?

No

Yes

Is there 2 VDC or less between

CN10A (+) and JPG (GND)(-) on

the indoor electronic control P.C.

board?

Is there 2 VDC or less between

CN10A (+) and JPG (GND)(-) on

the indoor electronic control P.C.

board?

Replace the indoor elec-
tronic control P.C. board.

No

Yes

No

Yes

Turn OFF the power supply.

Remove the short-circuit between outdoor terminal block S2 and S3.

Turn ON the power supply.

Is there rated voltage between indoor terminal block S1 and S2?

Yes

No