3. Outdoor unit failure mode table

POWER lamp

(Indoor unit)

Abnormal point

(Failure mode / protection)

LED indication

(Outdoor P.C. board)

Condition Remedy

Indoor/

outdoor unit

failure mode

recall function

Outdoor unit

failure mode

recall function

OFF None

(Normal)

2-time fl ash

2.5 seconds

OFF

Outdoor power system

Overcurrent protection stop is

continuously performed 3 times within

1 minute after the compressor gets

started.

Reconnect connectors.

Refer to 10-5. "How

to check inverter/

compressor".

Check stop valve.

3-time fl ash

2.5 seconds

OFF

Discharge temperature

thermistor

1-time fl ash every

2.5 seconds

Thermistor shorts or opens during

compressor running.

Refer to 10-5. "Check

of outdoor thermistors".

Defective outdoor

thermistors can be

identifi ed by checking

the blinking pattern of

LED.

Defrost thermistor (MUZ)

Fin temperature thermistor

3-time fl ash

2.5 seconds OFF

P.C. board temperature

thermistor

4-time fl ash

2.5 seconds OFF

Ambient temperature

thermistor

2-time fl ash

2.5 seconds OFF

4-time fl ash

2.5 seconds

OFF

Overcurrent 11-time

fl ash

2.5 seconds OFF

Large current fl ows into intelligent

power module.

Reconnect compressor

connector.

Refer to 10-5. "How

to check inverter/

compressor".

Check stop valve.

Compressor synchronous

abnormality (Compressor start-

up failure protection)

12-time fl ash

2.5 seconds OFF

Waveform of compressor current is

distorted.

Reconnect compressor

connector.

Refer to 10-5. "How

to check inverter/

compressor".

5-time fl ash

2.5 seconds

OFF

Discharge temperature

Temperature of discharge temperature

thermistor exceeds 241°F (116°C),

compressor stops.

Compressor can restart if discharge

temperature thermistor reads 212°F

(100°C) or less 3 minutes later.

Check refrigerant circuit

and refrigerant amount.

Refer to 10-5. "Check

of LEV".

6-time fl ash

2.5 seconds

OFF

High pressure
(MUZ)

Temperature of indoor coil thermistor

exceeds 158°F (70°C) in HEAT mode.

Temperature of outdoor heat exchanger

temperature thermistor exceeds 158°F

(70°C) in COOL mode.

Check refrigerant circuit

and refrigerant amount.

Check stop valve.

7-time fl ash

2.5 seconds

OFF

Fin temperature/ P.C. board

temperature

7-time fl ash

2.5 seconds OFF

Temperature of fi n temperature

thermistor on the inverter P.C. board

exceeds 167 ~ 176°F (75 ~ 80°C), or

temperature of P.C. board temperature

thermistor on the inverter P.C. board

exceeds 158 ~ 167°F (70 ~ 75°C).

Check around outdoor

unit.

Check outdoor unit air

passage.

Refer to 10-5. "Check

of outdoor fan motor".

8-time fl ash

2.5 seconds

OFF

Outdoor fan motor

Outdoor fan has stopped 3 times in a

row within 30 seconds after outdoor fan

start-up.

Refer to 10-5. "Check

of outdoor fan motor".

Refer to 10-5. "Check

of inverter P.C. board".

9-time fl ash

2.5 seconds

OFF

Nonvolatile memory data

5-time fl ash

2.5 seconds OFF

Nonvolatile memory data cannot be

read properly.

Replace the inverter

P.C. board.

10-time fl ash

2.5 seconds

OFF

Discharge temperature

Temperature of discharge temperature

thermistor has been 122°F (50°C) or

less for 20 minutes.

Refer to 10-5. "Check

of LEV".

Check refrigerant circuit

and refrigerant amount.

11-time fl ash

2.5 seconds

OFF

DC voltage

8-time fl ash

2.5 seconds OFF

DC voltage of inverter cannot be

detected normally.

Refer to 10-5. "How

to check inverter/

compressor".

Each phase current of

compressor

9-time fl ash

2.5 seconds OFF

Each phase current of compressor

cannot be detected normally.

12-time fl ash

2.5 seconds

OFF

Overcurrent Compressor open-

phase

10-time fl ash

2.5 seconds OFF

Large current fl ows into intelligent

power module (IPM).

The open-phase operation of

compressor is detected.

The interphase short out occurs in the

output of the intelligent power module

(IPM).

The compressor winding shorts out.

Reconnect compressor

connector.

Refer to 10-5. "How

to check inverter/

compressor".

14-time fl ash

2.5 seconds

OFF

Stop valve (Closed valve)

14-time fl ash

2.5 seconds OFF

Closed valve is detected by compressor

current.

Check stop valve

NOTE

: Blinking patterns of this mode differ from the ones of Troubleshooting check table (10-3.).