beautypg.com

Automatic phone test, The status light turns on, Sensor testing – GE 60-883-95R User Manual

Page 30: Press status. the panel says “sensor test ok, Phone communication testing, Phone test, Central station communication

background image

Sensor Testing

25

When the sensor supervision failure is fixed, the panel stops the trouble beeps and turns off the

Status light. Pressing Status during a sensor supervisory failure silences trouble beeps for 4

hours.

Automatic Phone Test

The panel verifies its ability to contact the central station every 1 to 254 days, depending on how

Option 14: Auto Phone Test is set.

¾

If the Auto Phone Test fails to contact the central station, the following occurs:

1. The Status light turns on.
2. If Option 25: Trouble Beeps is enabled, six trouble beeps will sound once a minute.
Pressing Status during an Auto Phone Test Failure silences trouble beeps for 4 hours.

Sensor Testing

We recommend that you test the sensors after all programming is completed and whenever a sen-

sor related problem occurs.

¾

To test sensors:

Note

Pressing the Menu button

cycles through 5 functions;

Phone Test, Sensor Test,

Medication Reminder, Add

Sensor and Delete all Sen-

sors. The panel will

announce the current func-

tion each time the button is

pressed.

1. Press the Menu button on the back of the panel until the panel announces “Sensor test. Press

Status to select.”

2. Press the Status button on the front of the panel to start a sensor test. The panel announces

“Sensor test is on, test sensor 1.”

3. Trip a sensor according to the instructions for that sensor or as described in Table 8.
4. The system will continue to prompt for sensors that have not yet been tested. When all the

sensors have been tested the panel will announce, “Sensor test complete, press status.”

Note

The panel will prompt for

each sensor in the order

they were programmed. If

there are no sensors pro-

grammed the panel says

“Function not available.”

5. Press Status. The panel says “Sensor test OK.”
For testing instructions for other sensors see the Installation Instructions for the sensor.

Phone

Communication

Testing

Perform phone tests to check the programmed phone numbers, off-site phone operation and

phone communication between the panel and the central station. While the following tests are

similar, they should all be performed in order to verify the system is working correctly.

Important !

The phone line must be plugged in for phone tests to be completed successfully.

Phone Test

Phone Test sends a test signal to the central monitoring station, pager and/or voice event notifica-

tion number. Perform a phone test to verify the panel dials the phone numbers correctly.

¾

To test the programmed phone numbers:

Note

If you don’t get the phone

test option, verify a phone

number (Options 3, 4, 5) is

programmed and Manual

Phone Test (Option 16) is

on.

1. Press the Menu button on the back of the panel once. The panel announces “Phone test. Press

Status to select.”

2. Press the Status button on the front of the panel. The panel says “Phone test is on” once a

minute while the phone test is being completed.

3. If all phone numbers are dialed successfully the panel says “Phone test OK.” If any phone

number is not dialed successfully the panel says “System phone communications failure.”

The panel will attempt each phone number 8 times.

Central Station Communication

¾

To test communication with the central station:

1. Call the central station and tell the operator you will be testing the system. If there are voice

event notification or pager numbers programmed notify them also.

2. Test each of the panic buttons to verify they are working correctly.
3. When you finish testing the system, call the central station to verify that the alarms were

received.