Digital energy, Lp series, 10 - specifications – GE Industrial Solutions LP11U 5-10kVA User Manual
Page 42

LX: OPM_LPU_11U_5K0_10K_1US_V030
40
GE DE LP 11U UPS: Installation / User Manual 3.0 (US)
Digital Energy
™
LP Series
g
UPS
Type
:
5-11U 6-11U 8-11U 10-11U
Output power (kVA/kW)
: 5/4
6/4.8
8/6.4
10/8
AC input voltage
: 120/208/240 Vac (120V only with step-up transformer for LP 5/6-11U)
Input frequency
: 60/50 Hz
AC output voltage
: 120/208/220/230/240V
Output frequency
: 60 or 50 Hz, std. 60 Hz; selectable on front
System efficiency (full load)
: 87%
Line input breaker (C-type)
: 32A
32A
50A
63A
Bypass input breaker (C-type)
: 32A
32A
50A
63A
Battery safety fuse (F4A)
: 30A
30A
30A
30A
Battery safety fuse (F4B)
: 30A (spare) 30A (spare) 30A
30A
Internal safety fuse (F5A)
: -
-
30A
30A
Internal safety fuse (F5B)
: 30A
30A
30A
30A
Input/output connectors
: terminals at rear of unit
INPUT
AC input voltage range (208V-240V)
at 100% load
: 162 - 285 V
at 50% load
: 146 - 285 V
at 20% load
: 133 - 285 V
AC input voltage range (120V, L5/6-11U)
at 100% load
: 81 - 141 V
at 50% load
: 72 - 141 V
at 20% load
: 66 - 141 V
Input frequency range
: 40-70 Hz
Input current wave form
: sinusoidal
Input power factor
:
≥
0.99
Max. input current at 100% load
120V : 43.3A
50.8A
n.a.
n.a.
208V
:
25.0A
30.0A
40.5
50.3
240V
:
21.4A
25.1 34.8 42.0
Inrush current
: none
Rectified DC voltage out
: 380 V
BATTERY CHARGER
Characteristic
: U/I-characteristic, constant current charging until boost/float voltage, then
constant voltage charging and boost charge mode for fast recharging of
batteries
DC input voltage range
: 350-450 V
DC output voltage at 20 °C
: float: 273 V boost: 295 V
Output current limit (Adc)
: 2.0
2.0
3.0
3.0
OUTPUT CONVERTER
Output power at pf. = 0.8, VA*
: 5000
6000
8000
10000
Semiconductor :
IGBT
AC output voltage
: 120/208/240V ± 1% static resistive load
120/208/240V ± 2% measured crest load 2.5:1
120/208/240V ± 2% dynamic mean deviation over one half cycle for 100% of
rated load applied or removed
Typical overload
: 110%
≥
20 minutes
(temp. dependent)
130%
≥
3.5 minutes
150%
≥
2 minutes
Output frequency
: 60 or 50 Hz selectable, ± 0.1%, unless synchronized with the utility
Freq. tracking range
: ± 2/4/6% of nominal, user selectable
Output wave form
: sine wave
Max. phase difference input-output
: max 7
°
Harmonic distortion
: 2% max. with linear load
Power factor range
: Any lagging or leading power factor permitted within the specified rating to
pf. 0.5
Output derating altitude
: Till 1000m no derating
Above 1000m 12.5% per 1000m, max. 4000m
Protection
: Automatic shut down (or transfer to bypass, if bypass is available) in case of
- low/high DC voltage
-
overtemperature
- overload / short circuit
The output is protected against connection to the utility supply
* according to EN 50091-1
10 - Specifications