LX: OPM_LPU_11U_5K0_10K_1US_V030
9
GE DE LP 11U UPS: Installation / User Manual 3.0 (US)
Digital Energy
™
LP Series
g
4.1 Transport
NOTE: Transport the UPS only in upright position. Check for sufficient floor and elevation loading
capacity. Move the UPS in its original package to the final destination room. Do not stack other
package on top.
4.2 Unpacking
Cut the two wrapping bands, and remove the shipping box. Loosen the four bolts with which the UPS is fixed to
the pallet. Remove the UPS from the pallet.
BE CAREFUL!
Pay attention to the HEAVY WEIGHT of the UPS when downloading the UPS
from the pallet! Never try to lift the unit by yourself!
The UPS is equipped with castors, which allow easy displacement of the unit. Please take appropriate
measures to avoid damage on vulnerable floors.
4.3 Package
Contents
The shipping box contains a LP-U UPS, a CD-ROM, an RS232 cable, a link (5/6kVA models only, see 4.5.3) a
safety guide and this manual. If the UPS is equipped with an RPA plug-in card (Redundant Parallel
Architecture, right option slot at the rear of the unit) the shipping box also contains a yellow network cable and
one bus terminator. Inspect the UPS for damage after unpacking. If any damage is present please notify the
carrier and place of purchase immediately.
4.4 Location
Please refer to section 1.3 of ‘IMPORTANT SAFETY INSTRUCTIONS’.
4.5 Installation
IMPORTANT
:
Before making any connection and switching on the LP UPS, please check the following conditions:
•
The voltage and frequency of your utility supply is 120/208/230/240 Vac
and 50 or 60 Hz; from the
factory the input and output of the UPS are set to 208 Vac / 60 Hz.
•
Be sure that the UPS is wired for the present utility voltage. This is indicated on the packaging of the
UPS, as well as at the I/O terminals.
•
Overcurrent protection for the AC circuit is to be provided by others.
•
CAUTION:
To reduce risk of fire, connect only to a circuit input/output provided with
branch circuit overcurrent protection in accordance with the National
Electrical Code, ANSI / NFPA 70, as indicated below:
UPS model
Input overcurrent protection
(Amps)
Output overcurrent protection
(Max. Amps)
Operating input voltage
120V 208V 240V 120V
(1 X)
120V
(2X)
208V 240V
LP
5-11U
35 30 40 20 25 20
LP 5-11U /120V
60
40
20
25
20
LP
6-11U
40 35 50 25 30 25
LP 6-11U /120V
70
50
25
30
25
LP
8-11U
60 45 70 35 40 35
LP 10-11U
70
60
80
40
50
40
Table 1. external input fuse value
4 - Installation