Appendix c.5.3 – FieldServer FS-8700-80 User Manual
Page 38
McQuay Micro Tech Open Protocol Driver Manual
Page 38 of 43
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Array Location Read/Write/Both Field Name
Number of Bytes Base Address Device Scaling Method
18
r
Circuit #1 Liquid Line Temperature
2
0x0479
6
19
r
Circuit #1 Previous Alarm
1
0x0833
1
20
r
Circuit #1 Status
1
0x0428
1
22
r
Circuit #1 Subcooling Temperature
2
0x049B
2
24
r
Circuit #1 Suction Temperature
2
0x0475
6
26
r
Circuit #1 Superheat Temperature
2
0x0493
2
28
r
Circuit #2 Condenser Approach Temperature
2
0x0499
2
30
r
Circuit #2 Condenser Pressure
2
0x0469
2
32
r
Circuit #2 Alarm Conditions: Condenser Pressure 2
0x082A
2
34
r
Circuit #2 Alarm Conditions: Evaporator Pressure 2
0x0828
2
36
r
Circuit #2 Alarm Conditions: Liquid Line Tempe
2
0x082E
6
38
r
Circuit #2 Alarm Conditions: Suction Temperature 2
0x082C
6
39
r
Circuit #2 Current Alarm
1
0x0832
1
41
r
Circuit #2 Evaporator Pressure
2
0x0465
2
43
r
Circuit #2 Liquid Line Temperature
2
0x047B
6
44
r
Circuit #2 Previous Alarm
1
0x0834
1
45
r
Circuit #2 Status
1
0x0429
1
47
r
Circuit #2 Subcooling Temperature
2
0x049D
2
49
r
Circuit #2 Suction Temperature
2
0x0477
6
51
r
Circuit #2 Superheat Temperature
2
0x0495
2
53
r
Compressor #1 Operating Hours
2
0x0862
1
55
r
Compressor #1 Starts
2
0x086A
1
57
r
Compressor #2 Operating Hours
2
0x0864
1
59
r
Compressor #2 Starts
2
0x086C
1
61
r
Compressor #3 Operating Hours
2
0x0866
1
63
r
Compressor #3 Starts
2
0x086E
1
65
r
Compressor #4 Operating Hours
2
0x0868
1
67
r
Compressor #4 Starts
2
0x0870
1
69
r
Condenser Entering Water Temperature
2
0x0470
6
71
r
Condenser Leaving Water Temperature
2
0x0472
6
73
r
Evaporator Entering Water Temperature
2
0x046E
6
75
r
Evaporator Leaving Water Temperature
2
0x0461
6
76
r
Heat/Cool Switch
1
0x08B4
1
78
r
OaT
2
0x047D
6
79
r
Stage of Capacity
1
0x042B
1
80
r
Unit % RLA
1
0x0474
1
81
r
Unit Status
1
0x0427
1
82
b
Clear Circuit #1 Alarm
1
0x091A
1
83
b
Clear Circuit #2 Alarm
1
0x091B
1
84
b
Condenser Leaving Water Temperature Setpoint 1
0x097D
1
85
b
Evaporator Entering Water Temperature Setpoint 1
0x090D
4
86
b
Evaporator Leaving Water Temperature Setpoint 1
0x0905
4
87
b
Maximum Water Reset Setpoint
1
0x090C
4
88
b
Network Command
1
0x044F
1
89
b
Network Demand Limit
1
0x044D
1
90
b
Network Leaving Water Temperature Reset
1
0x044E
1
91
b
Reset Option Setpoint
1
0x090B
1
Appendix C.5.3.
Equipment Type: 100CFC 100 Series Centrifugal Chiller
Array Location Read/ Write/ Both Field Name
Number of Bytes Base Address Device Scaling Method
1
r
Alarm Contact
1
0x0217
1
2
r
Approach Condenser
1
0x0418
1
3
r
Calculated Leaving Evaporator Temp Setpoint
1
0x0420