McQuay Micro Tech Open Protocol Driver Manual

Page 35 of 43

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Appendix C.3. McQuay Equipment Types recognized by the driver.

Code

Description

200CFC

200 Series Centrifugal Chiller

100CFC

100 Series Centrifugal Chiller

001ASC

Air Screw Chiller

000SCU

Self Contained Unit

0050RPC Reciprocating Chiller

Appendix C.4. Device Scaling Method

There are 5 device scaling methods. X refers to the raw value obtained from the McQuay device. The method that
will be applied to each field is shown in the following table.

Method Id. Device Scaling Method
1

X

2

X/10

3

(X–1000)/10

4

X/2

5

X-100

6

(X–100)/10

7

(X/5)+20

8

(X/5)+55

9

(X/5)

10

(X/5)-100

11

((X-51)*419)/51

12

(X-125)/500

13

(X*0.02)


Note that when device scaling is applied it is applied without consideration of the raw value. Where the raw value
has a special meaning (available in the McQuay packet documents for the equipment type of interest); this driver
does not apply any special consideration to these special values.

Appendix C.5. Data Field Name Tables

7

It is possible to read the device by specifying the address only. Refer to example in 0

Appendix C.5.1.

Equipment Type: 200CFC 200 Series Centrifugal Chiller

Array Location Read/Write/Both Field Name

Number of Bytes Base Address Device Scaling Method

1

r

Model

3

0x0A08

1

4

r

Refrigerant

1

0x0A0B

1

5

r

Units of Measure

1

0x0A0C

1

7

Additional information may be obtained from McQuay International. Request the following document: MicroTech® Series 200 Centrifugal

Chiller Data Communications Packet for Open Protocol™ Cent2_22.doc