CONFIGURING THE FIELDSERVER AS A MCQUAY MICRO TECH OPEN PROTOCOL CLIENT

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer. (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate
with a McQuay Micro Tech Open Protocol Server.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for McQuay Micro Tech Open Protocol communications, the driver independent FieldServer buffers
need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the
“Client Side Nodes” section, and the data required from the Servers needs to be mapped in the “Client Side Map
Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

6.1

Client Side Connection Parameters

Section Title
Connections
Column Title

Function

Legal Values

Port

Specify which port the device is connected to
the FieldServer

P1-P8, R1-R2

1

Baud*

Specify baud rate

300, 1200, 2400, 4800, 9600 (Vendor
limitation).

Parity*

Specify parity

Even (Vendor limitation)

Data_Bits*

Specify data bits

7 (Vendor limitation)

Stop_Bits*

Specify stop bits

1

Protocol

Specify protocol used

MCQ, McQuay

Poll Delay*

Time between internal polls

0-32000 s, 1s


Example

// Client Side Connections

Connections

Port

, Baud , Parity , Data_Bits , Protocol , Poll_Delay

P1

, 9600 , Even

, 7

, McQuay , 0.100s

1