McQuay Micro Tech Open Protocol Driver Manual

Page 31 of 43

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

4. Start McQuay Open Protocol Monitoring Software

5. Enter the User Name as “McQuay” and the password as ”SGC”

6. Once in the main menu, hit ‘F7’ to enter Advanced Features

7. Hit ‘F1’ to enter Read/Write Memory

8. Enter “b00.00” to change the Box Address (Node_HI and Node_LO) to “00”

9. Enter “w0A11 C1” to write C1 to memory address 0A11. This will set up the comm port configuration

with Port A as TTY and Port B as Master

10. Test if the wiring to the daisy chained devices is correct by doing the following:

o To read from a controller with the rotary hex switches set to “01”, change the box address to

01.00 and enter r0A11

o If you get a response, then it is wired correctly
o It is suggested that you read from each daisy chained controller

11. Shut down the McQuay Open Protocol Monitoring Software

12. Disconnect unit from the PC

13. Connect FieldServer to Port A (RS-232)