Server side connection paramaters – FieldServer FS-8700-80 User Manual
Page 21
McQuay Micro Tech Open Protocol Driver Manual
Page 21 of 43
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
7
CONFIGURING THE FIELDSERVER AS A MCQUAY MICRO TECH OPEN PROTOCOL
SERVER
7.1
Server Side Connection Paramaters
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the device is connected to
the FieldServer
P1-P8, R1-R2
3
Baud*
Specify baud rate
300, 1200, 2400, 4800, 9600 (Vendor
limitation)
Parity*
Specify parity
Even (Vendor limitation)
Data_Bits*
Specify data bits
7 (Vendor limitation)
Stop_Bits*
Specify stop bits
1(Vendor limitation)
Protocol
Specify protocol used
MCQ, McQuay
Example
// Server Side Connections
Connections
Port
, Baud , Parity , Data_Bits , Protocol , Stop_Bits , Poll_Delay
P1
, 9600 , Even
, 7
, McQuay , 1
, 0.100s
3
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.