Power connection and configuration

FortiGate-5050-R Chassis Guide
01-30000-87717-20090108

23

http://docs.fortinet.com/

Feedback

Figure 16: Connecting a FortiGate-5050 power input connector to a FortiGate-5053 power

converter tray

7 Make sure the power wires are secured to the chassis using the power wire fixture and

tie wraps if required.

8 If required, label the black wires -48V.
9 If required, label the red wires RTN.
10 Re-attach the protection plate to the FortiGate-5050 power input connector.
11 Attach the clear plastic cover to the back of the FortiGate-5053 power converter tray.
12 Connect the FortiGate-5053 power converter tray to AC power.

Only connect the power supplies that are installed in the FortiGate-5053 to AC power.
For example, if your FortiGate-5053 includes two FortiGate-5020/5050 power supplies,
the power supplies will be installed in slots 1 and 2. In this case you should only
connect AC in connectors 1 and 2 to AC power. If your FortiGate-5053 power converter
tray contains three power supples, connect all three AC in connectors to AC power.

The photograph in

Figure 17

shows the back panel of a FortiGate-5053 wired to provide

power to a FortiGate-5050 chassis. This photograph also shows the clear back cover of
the FortiGate-5053 installed. You should install this cover using the mounting hardware
provided. Install the cover after connecting the power but before turning the power on.

INPUT A

24

AMP

-48V

RTN (-DC IN)

Red RTN to

FortiGate-5053

RTN

Black -48V

VDC to

FortiGate-5053

-48 VDC

-48V

(-DC in)

(black)

Positive (RTN) (red)

Power wire

fixture

AC in

V+

(RTN)

(RED)

V-

-48V