Connecting the FortiGate-5050 chassis to data center DC power and data center ground

FortiGate-5050-R Chassis Guide

16

01-30000-87717-20090108

http://docs.fortinet.com/

Feedback

Figure 8: Connecting a FortiGate-5050 power input connector to data center DC power

To connect a FortiGate-5050 power input connector to data center DC power

You need the following tools and equipment to connect a FortiGate-5050 power input
connector to data center DC power:
• A number 2 Phillips screwdriver.
• An electrostatic discharge (ESD) preventive wrist or ankle strap with connection cord.
• One black AWG-14 stranded wire with terminal lugs attached and labelled -48V.
• One red AWG-14 stranded wire with terminal lugs attached and labelled RTN.
1 Attach the ESD wrist strap to your wrist and to an ESD socket or to a bare metal

surface on the chassis or frame.

2 Loosen the screws and remove the protection plate.
3 Insert the black -48V and red RTN wires through the power wire fixture (see

Figure 8

).

4 Connect the black -48V power wire from the data center DC power source to the

terminal on the FortiGate-5050 power input connector labelled (-DC in).

5 Connect the red RTN return wire from data center RTN to the terminal on the

FortiGate-5050 power input connector labelled RTN.

6 Make sure the power wires are secured to the chassis using the power wire fixture and

tie wraps if required.

7 If required, label the black wire -48V.
8 If required, label the red wire RTN.
9 Re-attach the protection plate to the FortiGate-5050 power input connector.

-48
(-DC in)

(black)

Positive

(RTN)

(red)

INPUT A

24

AMP

-48V

(-DC in) black to

Data Center -48VDC

Data Center

-48VDC

connector

RTN (positive)

red to Data
Center RTN

Data Center

RTN connector

Power wire

fixture

-48V

RTN (-DC IN)