Shelf alarm panel telco alarms – Fortinet FortiGate 5050-R User Manual
Page 11
FortiGate-5050 chassis
FortiGate-5050 shelf alarm panel
FortiGate-5050-R Chassis Guide
01-30000-87717-20090108
11
Figure 5: Connections between the shelf managers and the shelf alarm panel
Shelf alarm panel telco alarms
The shelf alarm panel telco alarm interface relay circuits are capable of carrying 60 VDC
or 1 A with a max. rating of 30 VA. The shelf alarm panel accepts timed pulse inputs for
clearing minor and major alarm states. Reset is accomplished by asserting a voltage
differential from 3.3 V to 48 V for between 200 and 300 ms. The acceptance voltage range
is from 0 to 48 VDC continuous (handles up to 60 VDC at a 50% duty cycle). The current
drawn by a reset input does not exceed 12 mA.
The alarm LED reset button activates the alarm cutoff (ACO) state for major, minor, and
user-defined alarms. You cannot reset critical alarms with the alarm LED reset button.
When the ACO state is activated, active alarm LEDs blink and all of the alarm relays are
deactivated. The alarm reset button activates the ACO state but does not clear the alarm
completely.
Figure 6: The telco alarm connector (DB-15 male)
5050SAP
SERIAL
1
SERIAL
2
ALARM
Primary Shelf Manager (Right)
I²C-Switch
PCA9545
Buffer
LTC4300
ShMM-500
el
b
a
n
E
yl
n
O-
r
et
s
a
M
s
u
b-
C²I
e
c
afr
et
nI
el
o
s
n
o
C
l
air
e
S
Secondary Shelf Manager (Left)
I²C-Switch
PCA9545
el
b
a
n
E
yl
n
O-
r
et
s
a
M
s
u
b-
C²I
e
c
afr
et
nI
el
o
s
n
o
C
l
air
e
S
Buffer
LTC4300
ShMM-500
0
H
C
3
H
C
0
H
C
3
H
C
1
9
15
8