2 facility power requirements and characteristics, Facility power requirements and characteristics – FUJITSU M3000 User Manual
Page 31

Chapter 2
Preparing to Install the Server
2-5
2.2.2.2
Facility Power Requirements and Characteristics
For proper redundancy, the facility must have two independent power sources. That
is, circuit breakers must be connected either to separate power company utility feeds
or to an uninterruptible power system (UPS). For power redundancy, the power
cables must not be connected to the same facility power source.
TABLE 2-3
Electrical Specifications
Item
Specification
100 to 120 VAC
200 to 240 VAC
Number of power cables
2 (1 cable for each power supply unit)
Power cord length
3 m/9.84 ft
Redundancy
1 + 1 redundant configuration
Input voltage
100 to 120 VAC
200 to 240 VAC
Rated current
*
* In a redundant configuration, the rated current per cable is half the value shown in
.
4.80 A
2.59A
Frequency
50/60 Hz
Power consumption (maximum)
470 W
460W
Apparent power
480VA
517VA
Heat dissipation
1,603.7 BTU/hr (1,692 KJ/hr)
1,569.6 BTU/hr (1,656 KJ/hr)
Power factor
0.98 (full configuration)
0.89 (full configuration)
TABLE 2-4
Power Cords and Connector Shape
Destination
Power cable type
Connector shape
Japan
NEMA 5-15 125V15A
IEC 60320 C13
North America
NEMA L6-15 250V15A
China
GB 2099.1
250V15A
Hong Kong
IEC60320-C14
250V15A
South Korea
IEC 60320-C14
250V15A