Chapter 2

Preparing to Install the Server

2-3

The environmental requirements to run the server might vary depending on the
elevation as listed in

TABLE 2-1

.

TABLE 2-2

lists the recommended values for the temperature and humidity in the

computer room.

TABLE 2-1

Ambient Environmental Requirements

Operating Range

Non-Operating Range

Optimum

Ambient

temperature

5˚C to 35˚C
(41˚F to 95˚F)

Unpacked
0˚C to 50˚C (32˚F to 122˚F)
Packed:
-20˚C to 60˚C (-4˚F to 140˚F)

21˚C to 23˚C
(70˚F to 74˚F)

Relative

humidity

*

* There is no condensation regardless of the temperature and humidity

20% RH to 80% RH

to 93% RH

45% RH to 50% RH

Altitude

restriction

† All altitudes are above sea level.

3,000m (10,000 ft)

12,000m (40,000 ft)

Temperature

conditions

5˚C to 35˚C (41˚F to 95˚F)
0 m to 500 m (0 ft to 1,640 ft)

5˚C to 33˚C (41˚F to 91.4˚F)
501 m to 1,000 m (1,644 ft to 3,281 ft)

5˚C to 31˚C (41˚F to 87.8˚F)
1,001 m to 1,500 m (3,284 ft to 4,921 ft)

5˚C to 29˚C (41˚F to 84.2˚F)
1,501 m to 3,000 m (4,925 ft to 9,843 ft)