Frymaster H50 Series User Manual
Page 13
1-7
Gas
Single
Vat
Dual
Vat
Natural Gas Lacq
(G20) under 20 mbar
7
7
Natural Gas Gronique *
(G25) under 25 mbar
10
10
Natural Gas Gronique
(G25) under 20 mbar
10
10
Butane/Propane
(G30) at 28/30 or 50 mbar
17
17
Propane
(G31) under 37 or 50 mbar
20
20
CE Standard
Burner Manifold Gas Pressures
for Fryers Manufactured After April 1999
Pressure (mbar)
* Belgian G25 = 7,0 mbar (single or dual)
Gas
Single
Vat
Dual
Vat
Natural Gas Lacq
(G20) under 20 mbar
7
6,5
Natural Gas Gronigue *
(G25) under 25 mbar
10
9
Natural Gas Gronigue
(G25) under 20 mbar
10
9
Butane
(G30) at 28/30 or 50 mbar
17
16,5
Propane
(G31) under 37 or 50 mbar
20,2
18,5
CE Standard
Burner Manifold Gas Pressures
for Fryers Manufactured Through April 1999
Pressure (mbar)
* Belgian G25 = 7,0 mbar (single) or 6,5 (dual)
Gas
Pressure
Natural
3" W.C.
0.73 kPa
Propane
8.25" W.C.
2.5 kPa
Non-CE Standard
Burner Manifold Gas Pressures
5. To adjust the burner gas pressure, remove the cap from the gas valve regulator and adjust to the
correct pressure.
Non-CE
Valve
Earlier Model CE Valve
Later Model
CE Valve
GAS VALVE REGULATOR CAP
6. Place the fryer power switch (and the gas valve in non-CE fryers) in the OFF position. Remove
the fitting from the pressure tap hole and reinstall the pressure tap plug.