Fluke 5020A User Manual
Page 91

Digital Communications Interface
Commands
6
6-21
Example: ALAR:TEMP1:UPP?
Response: 0
The TEMPerature suffix,
an upper temperature alarm event has occurred on the specified channel. A value of 0 is
returned if an upper temperature alarm event has not occurred on the specified channel.
ALARm:TEMPurature
Returns the state of the upper temperature alarm enable for the specified channel.
Example: ALAR:TEMP1:UPP:ENAB?
Response: 0
The TEMPerature suffix,
the upper temperature alarm is enabled. A value of 0 is returned if the upper temperature
alarm is disabled.
ALARm:TEMPurature
Sets the state of the upper temperature alarm enable for the specified channel.
Example: ALAR:TEMP1:UPP:ENAB 1
The TEMPerature suffix,
turns the upper temperature alarm on (1 or ON) or off (0 or OFF). This command may be
password protected (see Password Commands).
ALARm:TEMPurature
Returns the upper temperature alarm limit for the specified channel in degrees C or F.
Example: ALAR:TEMP1:UPP:LIM?
Response: 28.00
The TEMPerature suffix,
always in the current temperature units (C or F). Specifying the MIN, MAX, or DEF
parameter returns the minimum, maximum, or default value respectively.
ALARm:TEMPurature
Sets the upper temperature alarm limit for the specified channel in degrees C or F.
Example: ALAR:TEMP1:UPP:LIM 26.00
The TEMPerature suffix,
specifies the value for the upper temperature alarm limit. The
the current temperature units (C or F). Specifying the MIN, MAX, or DEF parameter sets
the upper temperature alarm limit to the minimum, maximum, or default value
respectively. This command may be password protected (see Password Commands).
ALARm:TIME:FIRSt?
Returns the time of the first alarm event.
Example: ALAR:TIME:FIRS?
Response: 15,43,13
The response is returned in the format,